Pducoldstartdelay, Power – APC Command Line Interface User Manual

Page 33

background image

Command Reference: Switched Rack PDU

Command Line Interface (CLI) User’s Guide

29

pducoldstartdelay

Syntax (to read the cold-start delay):

pducoldstartdelay

Syntax (to set the cold-start delay):

pducoldstartdelay {time|never}

Description:

Set or read the PDU cold-start delay

(the time that the Switched Rack PDU delays
applying power to the outlets after AC power has
been applied to the Switched Rack PDU).

Access:

Administrator and device manager

(device-only user)

Parameters:

Output format, reading the cold start delay:

OK
PDU_name: PDU coldstart delay is time seconds.

Output format, setting the cold start delay:

OK
PDU_name: Setting PDU coldstart delay to time
seconds.

Error Messages:

E101, E104

power

Syntax:

power

Description:

Reads the total power usage of the

Switched Rack PDU in watts and volt-amps.

Parameters:

None.

Access:

All three user types with access to the

CLI.

Output Format:

OK
power_in_volt-ampsVA
power_in_wattsW

Error Message:

101

time

The cold-start delay in seconds to set for the

Switched Rack PDU. Allowed values are 0

through 300.

never

Sets the Switched Rack PDU to keep its

outlets turned off after power is applied until

the outlets are explicitly turned on by the on

command.