Pducoldstartdelay, Power – APC Command Line Interface User Manual
Page 33

Command Reference: Switched Rack PDU
Command Line Interface (CLI) User’s Guide
29
pducoldstartdelay
Syntax (to read the cold-start delay):
pducoldstartdelay
Syntax (to set the cold-start delay):
pducoldstartdelay {time|never}
Description:
Set or read the PDU cold-start delay
(the time that the Switched Rack PDU delays
applying power to the outlets after AC power has
been applied to the Switched Rack PDU).
Access:
Administrator and device manager
(device-only user)
Parameters:
Output format, reading the cold start delay:
OK
PDU_name: PDU coldstart delay is time seconds.
Output format, setting the cold start delay:
OK
PDU_name: Setting PDU coldstart delay to time
seconds.
Error Messages:
E101, E104
power
Syntax:
power
Description:
Reads the total power usage of the
Switched Rack PDU in watts and volt-amps.
Parameters:
None.
Access:
All three user types with access to the
CLI.
Output Format:
OK
power_in_volt-ampsVA
power_in_wattsW
Error Message:
101
time
The cold-start delay in seconds to set for the
Switched Rack PDU. Allowed values are 0
through 300.
never
Sets the Switched Rack PDU to keep its
outlets turned off after power is applied until
the outlets are explicitly turned on by the on
command.