Quick Configuration for a Metered PDU
12
Basic and Metered Rack Power Distribution Unit
3. Use Telnet to access the
PDU
at its newly assigned
IP
address. For
example:
telnet 156.205.14.141
4. Use apc for both User Name and Password.
5. See “Control console” on this page to finish the configuration.
Control console
After you log on at the control console, as described in “Local access to
the control console” on page 11 or “Remote access to the control
console” on page 11:
1. Choose Network from the Control Console menu.
2. Choose
TCP/IP
from the Network menu.
3. If you are not using a
BOOTP or DHCP
server to configure the
TCP/IP
settings, select the Boot Mode menu. Select Manual boot
mode, and then press
E
SC
to return to the
TCP/IP
menu. (Changes
will take effect when you log out.)
4. Set the System
IP
, Subnet Mask, and Default Gateway address
values.
5. Press
C
TRL
-C
to exit to the Control Console menu.
6. Log out (option 4 in the Control Console menu).
Note
If you disconnected a cable during the procedure
described in “Local access to the control console” on
page 11, reconnect that cable and restart the associated
service.