beautypg.com

Ground-loop heat pump applications � caution, Table 2: antifreeze percentages by volume – Comfort-Aire HWW120 User Manual

Page 13

background image

12

Pre-Installation

Prior to installation, locate and mark all existing underground

utilities, piping, etc. Install loops for new construction before

sidewalks, patios, driveways, and other construction has

begun. During construction, accurately mark all ground loop

piping on the plot plan as an aid in avoiding potential future

damage to the installation.

Piping Installation

All earth loop piping materials should be limited to only

polyethylene fusion for inground sections of the loop.

Galvanized or steel fittings should not be used at any time

due to their tendency to corrode. All plastic to metal threaded

fittings should be avoided due to their potential to leak in

earth coupled applications and a flanged fitting substituted.

P/T plugs should be used so that flow can be measured

using the pressure drop of the unit heat exchanger in lieu of

other flow measurement means. Earth loop temperatures can

range between 25 to 110°F [-4 to 43°C], and 2.25 to 3 gpm of

flow per ton [2.9 l/m to 3.9 l/m per kW] of cooling capacity is

recommended in these applications. Upon completion of the

ground loop piping, pressure test the loop to assure a leak free

system. Horizontal Systems: Test individual loops as installed.

Test entire system when all loops are assembled. Vertical

U-Bends and Pond Loop Systems: Test Vertical U-bends and

pond loop assemblies prior to installation with a test pressure

of at least 100 psi [689 kPa].

Flushing the Earth Loop

Upon completion of system installation and testing, flush the

system to remove all foreign objects and purge to remove all

air. Flush the loop first with the unit isolated to avoid flushing

debris from the loop into the unit heat exchanger

Heat Controller, Inc.

WATER-TO-WATER (HWW) SERIES

Installation & Operation

Ground-Loop Heat Pump Applications

� CAUTION! �

The following instructions represent industry accepted

installation practices for Closed Loop Earth Coupled Heat

Pump Systems. They are provided to assist the contrac-

tor in installing trouble free ground loops. These instruc-

tions are recommendations only. State and Local Codes

MUST be followed and installation MUST conform to ALL

applicable Codes. It is the responsibility of the Installing

contractor to determine and comply with ALL applicable

Codes and Regulations.

Table 2: Antifreeze Percentages by Volume

Type

Min. Temp. for Low Temp. Protection

10°F

[-12.2°C]

15°F

[-9.4°C]

20°F

[-6.7°C]

25°F

[-3.9°C]

Methanol
100% USP

food grade

Propylene

Glycol
Ethanol*

25%
38%

29%

21%
25%

25%

16%
22%

20%

10%
15%

14%

* Must not be denatured with any petroleum based product

Antifreeze

In areas where minimum entering loop temperatures drop

below 40°F [5°C] or where piping will be routed through areas

subject to freezing, anti-freeze is needed. Alcohols and glycols

are commonly used as antifreezes, however your local sales

manager should be consulted for the antifreeze best suited

to your area. Freeze protection should be maintained to 15°F

[9°C] below the lowest expected entering loop temperature.

For example, if 30°F [-1°C] is the minimum expected entering

loop temperature, the leaving loop temperature would be

25 to 22°F [-4 to -6°C] and freeze protection should be at

15°F [-10°C] e.g. 30°F - 15°F = 15°F [-1°C - 9°C = -10°C]. All

alcohols should be premixed and pumped from a reservoir

outside of the building when possible or introduced under

water level to prevent fuming. Initially calculate the total

volume of fluid in the piping system using Table 1. Then use

the percentage by volume shown in Table 2 for the amount of

antifreeze. Antifreeze concentration should be checked from

a well mixed sample using a hydrometer to measure specific

gravity.

Low Water Temperature Cut-Out Setting CXM Control:

When an antifreeze is selected, the FP1 jumper [JW3] should be

clipped to select the low temperature (Antifreeze 15°F [-9.4°C])

setpoint to avoid nuisance faults. See Figure 5 [Page 14].

Table 1: Approximate Fluid Volume

(gallon) per 100' of Pipe

Fluid Volume (gal [liters] per 100’ [30 meters) Pipe)

Pipe

Size

Volume (gal) [liters]

Copper

1”

4.1 [15.3]

1.25”

6.4 [23.8]

2.5”

9.2 [34.3]

Rubber Hose

1”

3.9 [14.6]

Polyethylene

3/4” IPS SDR11

2.8 [10.4]

1” iPS SDR11

4.5 [16.7]

1.25” IPS SDR11

8.0 [29.8]

1.5” IPS SDR11

10.9 [40.7]

2” IPS SDR11

18.0 [67.0]

1.25” IPS SCH40

8.3 [30.9]

1.5” IPS SCH40

10.9 [40.7]

2” IPS SCH40

17.0 [63.4]

Unit Heat Exchanger

Typical

1.0 [3.8]

Flush Cart Tank

10” Dia x 3ft tall

[254mm x 91.4cm tall]

10 [37.9]

This manual is related to the following products: