Bell & Gossett V1001576 Suction Diffuser Plus User Manual
Page 12

1
2
3
4 5
6
7
8
B
A
C D
9
• A = To remove diffuser
• B = Distance to support leg
• C = Foot support, not furnished
• D = Support leg, not furnished
Figure 1: Working pressure 175 PSI (1207 KPa), 121°C
(250°F)
1.
System
2.
Warning label #V56871 installed here. If
missing it must be replaced.
3.
Inlet vanes
4.
Start-up strainer
5.
Orifice cylinder
6.
Cover
7.
Pump
8.
Gauge port
9.
Blowdown plug
1
2
3
4
5
Figure 2: Working pressure 300 PSI (2069 KPa), 121°C
(250°F)
1.
System
2.
Warning label #V56871 installed here. If
missing it must be replaced.
3.
Foot support, not furnished
4.
Adapter flange
5.
Pump
Size
Model Number
Dimensions in inches (mm)
A
B
Part Number C
Schedule 40
Diameter D
2x1.5
BA-3
5.15 (130.8)
3.81 (96.8)
A90982
3/4” (19.1)
2x2
BB-3
6.75 (171.5)
4.38 (111.3)
A90982
3/4” (19.1)
2.5x2
CB-3
6.75 (171.5)
4.38 (111.3)
A90982
3/4” (19.1)
2.5x2.5
CC-3
7.63 (193.7)
5.77 (146.6)
A90982
3/4” (19.1)
2.5x2.5 GXF
SDG-2.5
7.63 (193.7)
6.60 (167.6)
A90982
3/4” (19.1)
3x1.5
DA-3
6.63 (168.3)
4.38 (111.3)
A90982
3/4” (19.1)
3x2
DB-3
6.75 (171.5)
4.38 (111.3)
A90982
3/4” (19.1)
3x2.5
DC-3
7.63 (193.7)
5.77 (146.6)
A90982
3/4” (19.1)
4x2.5
EC-3
7.63 (193.7)
5.77 (146.6)
A90982
3/4” (19.1)
3x3
DD-3
8.75 (222.3)
7.02 (178.3)
A90883
1–1/4” (31.8)
3x3 GXF
SDG-3
8.75 (222.3)
7.66 (194.6)
A90883
1–1/4” (31.8)
4x3
ED-3
10.00 (254.0)
7.93 (201.4)
A90883
1–1/4” (31.8)
Installation
10