Electrical connection is to be carried out dependent on the type of switch (see type label) according
to the chart below. Wrong assignment of the connections may cause malfunctions or incorrect
switch outputs.

Plug
M 12x1
4-pin

Version with
1 switching output
(1 switch point SP1)

Version with 2 switching
outputs
(2 switch points SP1/SP2)

Pin 1

brown

+Ub (15... 32 V DC)

+Ub (15... 32 V DC)

Pin 2
white

-

SP2 (0.2 A max.)

NO

Pin 3

blue

0 V

0 V

Pin 4
black

SP1 (0.2 A max.)

NO

SP1 (0.2 A max.)

NO

1

4

2

3

+Ub

0 V

SP1

1

4

2

3

SP2

SP1

+Ub

0 V

WARNING

Check the operation of the switch regularly. If the switch does not work properly, stop operation
immediately!

6 Maintenance/Cleaning

The switch requires no maintenance.

CAUTION

The membrane keys may be damaged by the use of unsuitable cleaning agents. Do not use any
cleaning agents containing solvents or abrasive additives.

7 Technical

Data

UDS1V2

Measuring element

Piezoresistive silicon measuring cell with internal stainless steel
diaphragm or ceramic measuring cell

Measuring ranges

0 ... 10 bar to 0 ... 600 bar
0 ... 150 psi to 0 ... 9000 psi
relative pressure

Transistor switching outputs PNP

1 or 2 x NO contacts

Operating temperature range

-10... +70 C / +14... +158 °F

Media temperature range

-25 ... +100°C / -13 ... +212 °F

Process connection
(fitting "A" without adapter)

G1/4

Protection system/class

IP65/III

Electrical connection

Plug 4-pin, M 12x1

Auxiliary power

15... 32 V DC

For further technical data and options please refer to the data sheets

Operating and display elements/Dimensions

1

2

2

5

4

G ¼“

∅ 18.9 (7.37)

M12x1

Dimensions (example) in mm

Item 1: LED

green

Operational status
indicator

red

Item 2: Membrane keys

T1


T2

Programming keys
"Up“ and "Down“

appr

ox. 100

42

(1

6

.38)

14

(5

.46)

12

(4

.68)

11

(0

.2

9

)

∅ 24 (9.36)

SW 24

Sealing ring
DIN 3869