Troubleshooting, Product specifications – Automation Components A/RH-LCD Series User Manual
Page 4
![background image](/manuals/461547/4/background.png)
2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562
PH: (608) 831-2585 FAX (608) 831-7407
www.workaci.com
I0000150 Rev 4
Page 4 of 4
TROUBLESHOOTING
Problem:
No Reading
•
Check that you have the correct supply
voltage at the power terminal blocks.
•
Check that wiring configurations and all
DIP switch settings are as in Figures #1,
#2 and #7.
•
Verify that the terminal screws are all
connected tightly and that all of the wires
are firmly in place.
Erratic Readings
•
Verify that all of the wires are terminated
properly.
•
Make sure that there is no condensation
on the board.
•
Check that the input power is clean. In
areas of high RF interference or noise,
shielded cable may be necessary to
stabilize signal.
Inaccurate Readings
•
If you suspect that the transmitter is not
reading within the specified tolerance,
please contact the factory for further
assistance.
4-20m A Output: 250 Ohm Load 22 - 40
VDC / 22 - 28 VAC
RH M easurement Range
0 - 100% RH
4-20m A Output: 500 Ohm Load 24 - 40
VDC / 24 - 28 VAC (500 Ohm Load Max)
RH Accuracy @ 77
o
F (25
o
C)
± 1% over 20% span (between 20 to 90%)
± 2% , 3% , or 5% from 10 to 95%
Repeatability
0.5% RH
Operating Humidity Environment 0 to 95% RH
Supply Current
24mA M ax
Operating Temp. E nvironment
32 to 122
°F (0 to 50°C)
2-Wire, 4-20 mA
Storage Temp. Range
-40 to 160
°F (-40 to 71°C)
3-Wire, 4-20mA
Supply Voltage
RH Output
PRODUCT SPECIFICATIONS