+24 VDC Input Wiring Diagram
A/LCD-R 4-20 mA
(Loop Powered LCD Indicator)
A/RH Transmitter
+24 VDC Input / 4-20mA Output
10 Pin LCD Socket
RH 4-20 mA Output
+24 VDC Supply Voltage
RH 4-20 mA Output
to Controller
Optional Temperature
Sensor Output
to Controller (Resistive)
TTRO LCD Rev 7
- TEMP +
- LCD +
ZERO
SPAN
Factory Use Only
8
7
6
5
1
3
2
4
ON
Figure # 2
Push tab in and pull up on the sensor
cable to remove from J13 connector
Installation
Space Mount:
The RH transmitter should be placed away from excessive
moisture, corrosive fumes, vibration, or extremely high
temperatures. The base of the housing was designed to mount
over a standard 2” X 4” junction box. Mount the unit on an
indoor wall, approximately 4 to 6 feet above the floor.
1) Make sure the unit receives adequate airflow.
2) Connect the wires to the terminal block as shown
in the wiring connection section.
3) Snap the cover into position.
4) Turn out the two Allen screws at the bottom of
the enclosure until the cover cannot be removed.
OUTPUT SELECTIONS
Switches 6, 7, and 8 are used to set the output.
Refer to Figure #7 for switch settings.
Figure #7
Output Selection Switches (SW1)
4-20 mA Output
(Default)
ON
OFF
1
ON
3
2
5
4