Fault Tracing

The iX Panel T40 is working, but one or more keys are

not working

1. Check that the flex cables are correctly fitted.
2. Replace the front according to the

Replacing the Rear Cover

section.

The touch screen is malfunctioning or is not

responding at all

1. Re-calibrate the touch screen according to the

Calibrating the Touch Screen

sec-

tion.

2. Check that the flex cable is correctly fitted.
3. Replace the display of the operator panel according to the

Replacing the Display/Display Cable

section.

4. Check the touch interface on the power card.

Lines in display has wrong color or the display picture

is shifted

1. Check if the display has a wide vertical or horizontal area across the

display. It should be at least 2-3 cm wide with a grey or black color. See

Replacing the Display/Display Cable

for instructions on how to correct this.

2. Make sure the display cable is correctly fitted.
3. Make sure the display cable is not folded or damaged in any way. Replace the

display cable according to the

Replacing the Display/Display Cable

section.

The iX Panel T40 will not restart after changing a

component

1. Remove and insert the battery again.

Low battery / No battery

1. Check that the battery is correctly fitted in its holder.
2. If low battery/no battery voltage, replace the battery according to the

Replacing the Battery

section.

Beijer Electronics, MAEN004