15.4.2 H12 (Indoor/Outdoor Capacity Rank Mismatched)
Malfunction Decision Conditions
During startup, error code appears when different types of indoor and outdoor units are interconnected.
Malfunction Caused
Wrong models interconnected.
Wrong indoor unit or outdoor unit PCBs mounted.
Indoor unit or outdoor unit PCBs defective.
Indoor-outdoor unit signal transmission error due to wrong wiring.
Indoor-outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor
and outdoor units.
Troubleshooting
This manual is related to the following products:
See also other documents in the category Panasonic Fans:
- BG1002 (1 page)
- FV-08VKSL2 (16 pages)
- AC Fan Motor (ASEN9) (1 page)
- DC Axial Fans FBA11J10M (1 page)
- BM6025 (1 page)
- DC Axial Fans FBA06A (1 page)
- DC Axial Fans 2806RL (1 page)
- 26PEU1U6 (28 pages)
- 26PEU1U6 (198 pages)
- 26PEU1U6 (198 pages)
- 26PEU1U6 (64 pages)
- KE12NB41 (69 pages)
- KE12NB41 (20 pages)
- KE18NB4U (2 pages)
- KE12NB41 (24 pages)
- KE12NB41 (7 pages)
- 26PEU1U6 (53 pages)
- FV-10VSL2 (12 pages)
- FV-10VSL2 (8 pages)
- FV-08VKSE3 (12 pages)
- FV-08VRL1 (8 pages)
- FV-08VSL1 (15 pages)
- FV-40VQ3 (8 pages)
- FV-11VQC5 (11 pages)
- FV-20NLF1 (9 pages)
- EY7880LP2S (160 pages)
- EYFMA1JR (56 pages)
- EY6409NQKW (12 pages)
- EY6432NQKW (12 pages)
- FV-20NLF1 (9 pages)
- EY7940LR2S (50 pages)
- EYFLA6PR (56 pages)
- FV-07VFH3 (12 pages)
- KS18NB4UA (30 pages)
- KS18NB4UA (18 pages)
- KS18NB4UA (69 pages)
- FV-08VFL3 (16 pages)
- FV-13VKS3 (12 pages)
- FV-05VFM2 (12 pages)
- EY7411LA1S (44 pages)
- EY75A1X (56 pages)
- EYFEA1N2S (46 pages)
- EYFLA6P (56 pages)
- FV-11VF2 (14 pages)
- FV-11VF2 (11 pages)