4 compressor overheating prevention control, 6 low frequency protection control 1, 7 low frequency protection control 2 – Panasonic CS-XE9PKUA User Manual
Page 45
![background image](/manuals/453710/45/background.png)
45
13.1.4 Compressor
Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The
changes of frequency are as below.
If compressor discharge temperature exceeds 224.6°F (107°C), compressor will be stopped, occurs 4 times per
20 minutes, timer LED will be blinking. (“F97” is indicated.)
13.1.5 Low Pressure Prevention Control (Gas Leakage Detection)
Control start conditions
o
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.75A and 0.95A.
o
During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 7.2°F (4°C).
o
During Heating operations :
Indoor piping temperature - indoor suction is under 9°F (5°C).
Control
contents
o
Compressor stops (and restart after 3 minutes).
o
If the conditions above happen 2 times within 20 minutes, the unit will:
Stop
operation
Timer LED blinks and “F91” indicated.
13.1.6 Low
Frequency
Protection Control 1
When the compressor operate at frequency lower than 24 Hz continued for 20 minutes, the operation frequency
will be changed to 23 Hz for 2 minutes.
13.1.7 Low
Frequency
Protection Control 2
When all the below conditions comply, the compressor frequency will change to lower frequency.
Temperature, T, for:
Cooling/Soft Dry
Heating
Indoor intake air (°C)
T < 14 or T ≥ 30
T < 14 or T ≥ 28
Outdoor air (°C)
T < 13 or T ≥ 38
T < 4 or T ≥ 24
Indoor heat exchanger (°C)
T < 30
T ≥ 0
Temperature, T, for:
Cooling/Soft Dry
Heating
Indoor intake air (°F)
T < 57.2 or T ≥ 86.0
T < 57.2 or T ≥ 82.4
Outdoor air (°F)
T < 55.4 or T ≥ 100.4
T < 39.2 or T ≥ 75.2
Indoor heat exchanger (°F)
T < 86.0
T ≥ 32.0