beautypg.com

2. checklist before servicing – Panasonic KS12NB41A User Manual

Page 63

background image

Tubing precautions

Refrigerant R410A is more easily affected by dust or moisture compared with R22, thus be sure to temporarily

cover the ends of the tubing with caps or tape prior to installation.

Never use 0.0276" (0.7 mm)-thick copper tubing or tubing which is less than 0.0315" (0.8 mm) in thickness, since

air conditioners with R410A are subject to higher pressure than those using R22 and R407C.

No addition of compressor oil for R410A

No additional charge of compressor oil is permitted.

No use of refrigerant other than R410A

Never use a refrigerant other than R410A.

If refrigerant R410A is exposed to fire

Through welding, etc., toxic gas may be released when R410A refrigerant is exposed to fire. Therefore, be sure

to provide ample ventilation during installation work.

Caution in case of R410A leak

Check for possible leak points with the special leak detector for R410A. If a leak occurs inside the room,

immediately provide thorough ventilation.

A

D

Flare tool for R410A

A

D

Conventional flare tool (R22)

Spacer

11-2. Checklist before Servicing

Use a clutch-type flare tool for R410A or the conventional flare tool. Note that sizes of the resultant flares differ

between these two tools. Where a conventional flare tool is used, make sure to observe A Specification (amount of

extrusion) by using the flare spacer.

Size of flare

Specification A

Diameter of tube D

Dia.1/4" (6.35 mm)

Dia.3/8" (9.52 mm)

Dia.1/2" (12.7 mm)

Dia.5/8" (15.88 mm)

Flare tool for R410A

Conventional flare tool (for R22)

0 to 0.0196"

(0 to 0.5 mm)

0.0472"

(1.2 mm)

63

This manual is related to the following products: