4 cn – suppression of no reads, 5 nid- failure protection – AEG COMPACT READER ARE I2 User Manual
Page 17

Manual
Page 17 / 33- Revision 01
ARE I2 / RS 232 – Installation Guide
AEG
Identifikationssysteme GmbH
Söflinger Straße 100
D-89077 Ulm
Tel. ++49(0)731-933-1340/1877
Fax ++49(0)731-933-1855
e-mail: [email protected]
Input format:
CID
Parameter:
Value
Function
0
no filter function , (default value)
1
suppression of repeatedly read IDs
Please note: The CID parameter is only active, if the GT-Command is applied or the reader is
in the Continuos Reading Mode. In the MD 2 anyway a
6.4 CN – Suppression of No Reads
Through the setting CN=1 all NoRead results are suppressed on the serial interface..
Input format:
CN
Parameter:
Value
Function
0
issue NoReads on serial interface; (default value)
1
suppress NoReads on interface
Output (example): 0
Please note: The CN parameter is only active, if the GT-Command is applied or the reader is in
the Continuos Reading Mode. In the MD 2 any way a
6.5 NID- Failure Protection
NID specifies the number of identical transponder numbers, which have to appear for the
result “successful reading“ within a reading cycle. In the setting NID = 1, two successive
readings have to show the same transponder number.
Input format:
NID
Parameter:
Value
Function