5.0 Operation

5.4 Line voltage bar graph

The line voltage bar graph displays the UPS's input voltage in discrete steps. Line voltage
is displayed when the

I/Test

pushbutton is pressed and held. The example above shows

that the UPS's input line voltage is between 116 and 123 Vac (120 Vac version UPS, see
table for values for other versions). If no bars are illuminated, and the UPS is plugged into
a known working wall outlet, the line voltage is extremely low. Low input voltage could
be a result of an overloaded branch circuit, a misadjusted service pole transformer or
intentional local service brownout. The UPS will compensate for this problem by
boosting the load voltage supplied to your computer equipment. If all six bars are
illuminated, the line voltage is high and should be checked by a qualified electrician.

5.5 Audible alarm

The UPS contains a beeper that emits sound through the ventilation openings. Events
that cause the beeper to sound are listed below.

5.5.1 On-battery operation

The UPS emits four short beeps every 30 seconds following failure of the utility. The
audible alarm is silenced until the next utility failure when the

I/Test

pushbutton is

pressed.

5.5.2 Low battery

During an extended utility failure, the UPS will eventually emit continuous beeps to
indicate that the UPS will soon shut down due to battery capacity exhaustion. The low
battery warning cannot be muted.

Bar increments versus

version type

120 Vac

208 Vac

220/230/

240 Vac

130

237

260

123

225

246

116

212

232

110

200

220

104

187

208

98

175

196