INSTALLATION (cont.)
Figure 2
Adjust the regulator(s) as needed to comply with the pressures indicated on the
griddle orifice and pressure specification label. See Figure 2 for the orifice and pressure
specification data.
Figure 3
The system gas supply pressures for the main and pilot burners should be verified
with a manometer while the appliance is operating in a maximum load condition. A
1/8” NPT tap is provided in the front of the main regulator valve, to measure the main
burner supply pressure. A second ¼” NPT tap is located just to the right of the pilot
burner regulator for measurement of the pilot burner supply pressure. See Figure 3 for
the pressure tap locations. Use a pipe joint compound or sealant designed for use with
liquid petroleum gas when replacing the
1/8
” NPT plug or the ¼” NPT plug.
NOTE: Do not use an excessive amount of sealant, in order to prevent potential
obstruction of orifices and control valves.
1/8” NPT
1/4” NPT