2. Technical Gas Data

a. Gas Specifications

b. Gas Connections:

Inlet connection ------------ 3/4-inch N.P.T.
Inlet supply size ------------ 3/4-inch N.P.T. (minimum)
Btu/hr input (per dryer) --- 200,000 (50,400 kcal/hr)

1) Natural Gas

Regulation is controlled by the dryer’s gas valve’s internal regulator. Incoming supply pressure must
be
consistent between a minimum of 6.0 inches (14.92 mb) and a maximum of 12.0 inches (29.9 mb)
water column pressure (W.C.).

2) Liquid Propane (L.P.) Gas

Dryers made for use with L.P. gas have the gas valve’s internal pressure regulator blocked open so
that the gas pressure must be regulated upstream of the dryer. The pressure measured at each gas
valve pressure tap must be a consistent 10.5 inches (26.1 mb) water column. There is no regulator
or regulation provided in an L.P. dryer. The water column pressure must be regulated at the source
(L.P. tank) or an external regulator must be added to each dryer.

T

YPE OF

G

AS

L.P.

Conversion

Kit

Part Number

MODEL

NUMBER

BTU

Per Hour

Rating

kcal/hr

Rating

Natural

Liquid Propane

Qty. D.M.S.*

Part

Number

Qty. D.M.S.*

Part

Number

MLG-75

200,000

50,400

4

#

29

140820

4

#47

140805

881231

Shaded area is stated in metric equivalent

* Drill Material Size (D.M.S.) equivalents are as follows:

Natural Gas ............... #29

= 0.1360” (3.4544 mm).

Liquid Propane Gas .. #47

= 0.0785” (1.9939 mm).

TYPE OF GAS

NATURAL

LIQUID PROPANE

Manifold Pressure*

3.5 inches W.C.

8.7 mb

10.5 inches W.C.

26.1 mb

In-Line Pressure

6.0 - 12.0 inches W.C.

14.92 - 29.9 mb

11.0 inches W.C.

27.4 mb

Shaded areas are stated in metric equivalents

* Measured at outlet side of gas valve pressure tap when gas valve is on.