* AWG Stranded Type Wire for individual lengths less than 100 feet (30.48 meters).

NOTE: Contact factory for electrical information not listed.

NOTE: Manufacturer reserves the right to make changes in specifications at any time without notice or

obligation.

Providing local codes permit, power to the dryer can be made by use of a flexible U.L. listed power cord
or pigtail (wire size must conform to the rating of the dryer), or the dryer can be hard wired directly to
the service breaker panel. In both cases, a strain relief must be installed where the wiring enters the
dryer.

E

LECTRIC

S

ERVICE

S

PECIFICATIONS

(P

ER

T

UMBLER

)

A separate circuit breaker must be provided for each tumbler/pocket.

NOTE:

Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct

breaker size according to appliance amp draw rating and type of breaker used.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP

DRAW

MINIMUM

WIRE SIZE*

CIRCUIT

BREAKER

120

2

9.8

12

15