Configuration Settings
8
Smart-UPS RT SURTA1500XL/SURTA1500XLJ/SURTA2000XL Uninterruptible Power Supply User Manual
Utility Voltage Measurement
1. Press and hold the
button to view the utility voltage bar graph indicator.
2. After a few seconds, this five-LED Battery Charge
indicator will show the utility input
voltage.
3. Refer to the appropriate voltage (100 or 120) reading. Values are not listed on the UPS. The
actual input voltage is between the displayed value on the list and the next higher value.
Configuration Settings
Settings are adjusted through PowerChute software, optional SmartSlot accessory cards, or in terminal
mode.
Feature Display
Feature Title
Description
Diagnostic Utility
Voltage
The UPS has a diagnostic feature that indicates the utility voltage
coming into the UPS. The UPS starts a self-test as part of this
procedure. The self-test does not affect the voltage display. See
“Troubleshooting,” beginning on page 12 for additional informa-
tion.
Function
Factory Default
User Selectable
Choices
Description
Automatic
Self-Test
Every 14 days
(336 hours)
• Every 7 days
(168 hours)
• Every 14 days
(336 hours)
• On start up only
• No self-test
Set the interval at which the UPS will execute a
self-test.
UPS ID
UPS_IDEN
Up to eight characters
(alphanumeric)
Uniquely identify the UPS, (i.e. server name or
location) for network management purposes.
Date of Last
Battery
Replacement
Manufacture Date mm/dd/yy
Reset this date when you replace the battery
module.
Minimum Capacity
Before Return from
Shutdown
0 percent
• 0%
• 15%
• 30%
• 45%
• 60%
• 75%
• 90%
Specify the percentage to which batteries will
be charged following a low battery shutdown
before powering connected equipment.
Alarm Delay
Enable
• Enable
• Mute
• Disable
Mute ongoing alarms or disable all alarms per-
manently.
Shutdown Delay
90 seconds
• 0 s
• 90 s
• 180 s
• 270 s
• 360 s
• 450 s
• 540 s
• 630 s
Set the interval between the time when the
UPS receives a shutdown command and actual
shutdown.
118.0
100V
108.7
99.3
90.0
80.6
138.2
120V
128.8
119.5
110.1
100.8