beautypg.com

Utility voltage measurement, Configuration settings – American Power Conversion SURTA1500XL User Manual

Page 8

background image

Configuration Settings

8

Smart-UPS RT SURTA1500XL/SURTA1500XLJ/SURTA2000XL Uninterruptible Power Supply User Manual

Utility Voltage Measurement

1. Press and hold the

button to view the utility voltage bar graph indicator.

2. After a few seconds, this five-LED Battery Charge

indicator will show the utility input

voltage.

3. Refer to the appropriate voltage (100 or 120) reading. Values are not listed on the UPS. The

actual input voltage is between the displayed value on the list and the next higher value.

Configuration Settings

Settings are adjusted through PowerChute software, optional SmartSlot accessory cards, or in terminal
mode.

Feature Display

Feature Title

Description

Diagnostic Utility
Voltage

The UPS has a diagnostic feature that indicates the utility voltage
coming into the UPS. The UPS starts a self-test as part of this

procedure. The self-test does not affect the voltage display. See
“Troubleshooting,” beginning on page 12 for additional informa-
tion.

Function

Factory Default

User Selectable

Choices

Description

Automatic
Self-Test

Every 14 days
(336 hours)

• Every 7 days

(168 hours)

• Every 14 days

(336 hours)

• On start up only
• No self-test

Set the interval at which the UPS will execute a
self-test.

UPS ID

UPS_IDEN

Up to eight characters
(alphanumeric)

Uniquely identify the UPS, (i.e. server name or
location) for network management purposes.

Date of Last
Battery

Replacement

Manufacture Date mm/dd/yy

Reset this date when you replace the battery
module.

Minimum Capacity
Before Return from

Shutdown

0 percent

• 0%
• 15%
• 30%
• 45%

• 60%
• 75%
• 90%

Specify the percentage to which batteries will
be charged following a low battery shutdown

before powering connected equipment.

Alarm Delay

Enable

• Enable
• Mute

• Disable

Mute ongoing alarms or disable all alarms per-
manently.

Shutdown Delay

90 seconds

• 0 s
• 90 s
• 180 s
• 270 s

• 360 s
• 450 s
• 540 s
• 630 s

Set the interval between the time when the
UPS receives a shutdown command and actual
shutdown.

118.0

100V

108.7
99.3
90.0
80.6

138.2

120V

128.8
119.5
110.1
100.8

This manual is related to the following products: