Installation
Smart-UPS RT SURTA1500XL/SURTA1500XLJ/SURTA2000XL Uninterruptible Power Supply User Manual
3
1. Connect equipment to PDU receptacles .
2. If applicable, connect equipment to the serial or USB com port .
3. Connect ground cable of voltage surge-suppression equipment or the optional Smart-UPS RT
battery pack to the TVSS screw .
4. Add optional accessories to the Smart-Slot .
a. Remove the cover and screws. Discard or save cover. Do not attempt to reinstall it.
b. Refer to the accessory manual to install equipment.
If Required, Connect the Emergency Power Off (EPO) Feature
EPO terminal
The Emergency Power Off (EPO) terminal allows the user to connect
the UPS to the central EPO system.
N
OTE
: Adhere to national and local codes when wiring the EPO switch.
TVSS screw
The UPS features a Transient Voltage Surge-suppression (TVSS) screw
located on the rear panel, for connecting the ground cable on surge sup-
pression devices such as telephone and network line protectors.
N
OTE
: Prior to connecting the grounding cable, disconnect the UPS
from the utility power outlet and turn off the UPS.
External battery
pack connector
Optional Smart-UPS RT external battery packs provide extended run-
time during power outages. These units support up to ten external bat-
tery packs.
N
OTE
: See the APC web site,
www.apc.com
for information on the
external battery pack, SURTA48XLBP or SURTA48XLBPJ.
PDU Receptacles Connect equipment to the Power Distribution Unit (PDU) receptacles on
the rear of the UPS.
Caution
The EPO interface is a safety extra low voltage (SELV) circuit. Connect it only to other
SELV circuits. To avoid damage to the UPS, do not connect the EPO interface to any
circuit other than a closure type circuit, properly isolated from the utility.
Connectors
Type
Description