Caution – Allied Air Enterprises WARM AIR GAS FURNACE 92G1UH User Manual
Page 33

506724-01
Page 33 of 57
Issue 1108
Do not use copper tubing or existing copper condensate
lines for drain line.
CAUTION
Condensate line must slope downward away from the trap
to drain. If drain level is above condensate trap, condensate
pump must be used. Condensate drain line should be routed
within the conditioned space to avoid freezing of condensate
and blockage of drain line. If this is not possible, a heat
cable kit may be used on the condensate trap and line.
Heating cable kit is available in various lengths; 6 ft. (1.8 m)
- kit no. 26K68; 24 ft. (7.3 m) - kit no. 26K69; and 50 ft. (15.2
m) - kit no. 26K70.
FIGURE 44
CONDENSATE TRAP LOCATIONS
(Unit shown in upflow position with remote trap)
5’ max.
To Drain
*PVC Pipe Only
Field−Provided Vent
Min. 1" Above Condensate
Drain Connection
1" Min.
Trap can be installed a
maximum 5’ from furnace.
*Piping from furnace must slope down a minimum
of 1/4" per ft. toward trap.
CAUTION
A separate drain line must be run to the drain from
the condensate trap to ensure proper drainage and
pressure switch operation. DO NOT connect the
condensate trap drain into the drain line from the
evaporator coil.
FIGURE 45
Unit with Cooling Coil
Drain
Condensate trap and
evaporator coil must
be drained separately
as shown.
Field−Provided
Vent
Drain
Field−Provided
Vent
FIGURE 46
CONDENSATE TRAP LOCATIONS
(Unit shown in horizontal right−hand discharge position)
5’ max.
to drain
*PVC Pipe Only
4−1/2"
Min.
Field−Provided Vent
Must Not Interfere With
Service To The Unit
*Piping from furnace must slope down a minimum of 1/4" per ft. toward trap.