SDM-AO4 Four Channel Analog Output
12
16: Z=X+F (P34)
; Add 360 to the current reading
1: 9
X Loc [ WD_0_540 ]
; otherwise, the current reading
2: 360
F
; is left alone
3: 9
Z Loc [ WD_0_540 ]
17: End (P95)
18: End (P95)
; Scale the measurements for the SDM-AO4 to output 0 to 1000 mV
19: Z=X*F (P37)
; Scale WS: 0-50 mps = 0-1000 mV
1: 1
X Loc [ WS_ms ]
2: 20
F
3: 5
Z Loc [ WSoutput ]
20: Z=X*F (P37)
; Scale WD: 0-540 deg = 0-1000 mV
1: 9
X Loc [ WD_0_540 ]
2: 1.859
F
3: 6
Z Loc [ WDoutput ]
21: Z=X+F (P34)
; Scale Temperature: -40-60 deg C = 0-1000 mV
1: 3
X Loc [ Temp_C ]
2: 40
F
3: 7
Z Loc [ TempOut ]
22: Z=X*F (P37)
1: 7
X Loc [ TempOut ]
2: 10
F
3: 7
Z Loc [ TempOut ]
23: Z=X*F (P37)
; Scale RH: 0-100 % RH = 0-1000 mV
1: 4
X Loc [ RH ]
2: 10
F
3: 8
Z Loc [ RHout ]
; Send mV outputs to SDM-AO4
24: SDM-AO4 (P103)
1: 4
Reps
2: 30
SDM
Address
3: 5
Loc [ WSoutput ]
End Program