SDM-AO4 Four Channel Analog Output

12

16: Z=X+F (P34)

; Add 360 to the current reading

1: 9

X Loc [ WD_0_540 ]

; otherwise, the current reading

2: 360

F

; is left alone

3: 9

Z Loc [ WD_0_540 ]


17: End (P95)

18: End (P95)

; Scale the measurements for the SDM-AO4 to output 0 to 1000 mV

19: Z=X*F (P37)

; Scale WS: 0-50 mps = 0-1000 mV

1: 1

X Loc [ WS_ms ]

2: 20

F

3: 5

Z Loc [ WSoutput ]


20: Z=X*F (P37)

; Scale WD: 0-540 deg = 0-1000 mV

1: 9

X Loc [ WD_0_540 ]

2: 1.859

F

3: 6

Z Loc [ WDoutput ]


21: Z=X+F (P34)

; Scale Temperature: -40-60 deg C = 0-1000 mV

1: 3

X Loc [ Temp_C ]

2: 40

F

3: 7

Z Loc [ TempOut ]


22: Z=X*F (P37)
1: 7

X Loc [ TempOut ]

2: 10

F

3: 7

Z Loc [ TempOut ]


23: Z=X*F (P37)

; Scale RH: 0-100 % RH = 0-1000 mV

1: 4

X Loc [ RH ]

2: 10

F

3: 8

Z Loc [ RHout ]


; Send mV outputs to SDM-AO4

24: SDM-AO4 (P103)
1: 4

Reps

2: 30

SDM

Address

3: 5

Loc [ WSoutput ]


End Program