CS431 Submersible Pressure Transducer

The best method for minimizing ground loops is to tie all equipment (sensors,
dataloggers, external power sources and any other associated equipment) to a
single common grounding point.

To prevent grounding issues, do the following:

(1) Attach the sensor cable shield (the wrapped shield inside the cable) to the

power ground (G terminal) on the datalogger.

(2) Use a 12 AWG or larger wire to connect the datalogger’s grounding lug

with a grounding rod that has been driven into the earth.

(3) If using an external power supply, tie the power supply and datalogger to

the same earth ground.