Chatsworth Products N-Series TeraFrame® Gen 3 Network Cabinet User Manual
Page 12
![background image](/manuals/415760/12/background.png)
12
Floor Attachment Bracket
The mounting locations for the brackets are shown in the figure below.
Attach the cabinet to the floor with 3/8” or M10 hardware appropriate for your type of flooring.
Bonding the cabinet to the telecommunications ground
N-‐Series TeraFrame Cabinets should be bonded to the telecommunications ground. The top panel,
side panels, doors and mounting rails on the TeraFrame cabinet are electrically bonded to the frame. A
ground strap bonds the panels and doors to the frame. In order to bond the cabinet to the
telecommunications ground, use the Ground Terminal Block (included) to connect a bonding conductor
(ordered separately) to the telecommunications ground or signal reference grid. Remove the mask
sticker at desired grounding location and apply generous coating of gray antioxidant. For top location,
remove hole plug and route the bonding conductor through frame top first. Secure grounding wire to
the terminal block. Attach the block to the cabinet frame with an 8 mm wrench using two M5 bolts
and nuts.