beautypg.com

1000-0193_a4-17 – Samlex America SA-2000K User Manual

Page 17

background image

www.samlexpower.com

3-6. AC Safety Grounding

The AC output ground wire should go to the grounding point for your loads

(for example, a distribution panel ground bus).

3-6-1. Neutral Grounding (GFCI’S):

3-6-1-1.

120V models: The neutral conductor of the AC output circuit

of the Inverter is automatically connected to the safety ground during

inverter operation. This conforms to National Electrical Code

requirements that separately derived from AC sources (such as

inverters and generators) which have their neutral conductors tied to

ground in the same way as the neutral conductors from the utility tied

to ground at the AC breaker panel. For models configured with a

transfer relay, while AC utility power is present and the Inverter is in

bypass mode, this connection (the neutral of the Inverter’s AC output

to input safety ground) is not present so that the utility neutral is only

connected to ground at your breaker panel, as required.

Ground Fault Circuit Interrupters (GFCI)

Installations in Recreational Vehicles (for North American approvals) will

require GFCI protection of all branch circuit connected to the AC output of

the hardwire terminal equipped with Inverter. In addition, electrical codes

require GFCI protection of certain receptacles in residential installations.

While the pure sine wave output of the Inverter is equivalent to the waveform

provided by utilities, compliance with UL standards requires us to test and

recommend specific GFCI.

Samlex America Inc. has tested the following GFCI – protected 20A

receptacles and found that they functioned properly when connected to the

output of the Inverter.

15