3-5. DC Wiring Connections

Follow this procedure to connect the battery cables to the DC input terminals

of the Inverter. The cables should be as short as possible (less than 10 feet /

3 meters ideally) and large enough to handle the required current in

accordance with the electrical codes or regulations applicable to the

installation. Cables that are not an adequate gauge (too narrow) or too long

will deteriorate inverter performance such as poor surge capability and

frequent low-input voltage warnings and shutdowns.

These low input voltage warnings are due to DC voltage drop across the

cables from the inverter to the batteries. The longer and narrower the cables,

the greater the voltage drop.

Increasing DC cable size helps improve the situation. SAMLEX AMERICA

INC. recommends the following cables for optimum inverter performance.

Model No

Wire AWG

Inline Fuse

SA-2000K-112

# 2/0

250 A

SA-2000K-124

# 1/0

125 A

3-5-1. Connect the cables to the power input terminals on the rear panel of

the inverter. The red terminal is represents positive (+) and black

terminal represents negative (-). Insert the cables into the terminals

and tighten the screw to clamp the wires securely.

Ensure all the DC connections are tight (torque to

9 – 10 ft-lbs, 11.7 – 13 Nm). Loose connections may

cause overheat and fire.

WARNING!