A suitable Main Gas Pressure Regulator should be installed as shown in Figures 1 or 2
Choose a regulator(s) to adjust the available gas pressure to the pressure shown in SPECI-
FICATIONS, page 2.
CAUTION: The regulated gas pressures must not exceed 14"W.C. or Main
Automatic Gas Valve and Ignitor Regulator will be damaged. If excessive gas pressure
is prevalent, the regulator must be a tight shut-off type to prevent high pressures from
developing during stand-by.
4
Part 1 Installation
Table 2: Firing Rate Curves
V Piping Continued
PROPANE Gas
2,500 BTU / Cu. Ft.
(with 5/8" Main Gas Port)
NATURAL Gas
1,000 BTU / Cu. Ft.
(with Main Gas Tube
only, no Gas Port)
Manifold Gas Pressure in Inches W. C.
Input in MBH
Input in MBH
Input
Adjuster Setting in Number of
T
urns From Full Closed
Input
Adjuster Setting in Number of
T
urns From Full Closed
Manifold Gas Pressure in Inches W. C.