MVP-RPx-xxx - The title parameter is fixed. It displays the model number and the firmware version.
RAMP TIME FACTOR
– Sets the rate of change for the output current. If the Ramp Time Factor is x1, the ramp
time will match the ramp time settings. If it is set to 1/10, the ramp time will be 1/10 of the ramp time setting.
RAMP UP/DOWN TIME - Sets the rate of change for Output current.
For RP1, the output current increases from Minimum to Maximum.
For RP2, the output current is initially set to the Minimum.
The output current increases from Minimum to Maximum within the Ramp Up time when switching ON
“ENABLE” switch.
The output current decreases from Maximum to Minimum within the Ramp Down time when switching
OFF “ENABLE” switch.
MIN OUTPUT - Sets the minimum output current (milliamps, amps for -12A,-25A). The value in the brackets is the
present output current.
MAX OUTPUT - Sets the maximum output current (milliamps, amps for -12A,-25A). The value in the brackets is the
present output current.
DITHER FREQ.
– Options: 80, 100, 120, 140, 160, 180, 200, 220, 240, 260, 280, 300, (Select OFF for 1000Hz).
Set the PWM or dither frequency according to the valve specifications. This parameter is variable.
OUTPUT CURRENT - Displays the present output current. This parameter is a monitor type.
SUPPLY VOLTAGE - Displays the
module’s power supply voltage. It is helpful for troubleshooting. This parameter
is a monitor type.
FAULT STATUS - The STATUS LED will flash red 2 times for Coil Open and 3 times for Coil Short.