0 troubleshooting, 0 troubleshooting table, Operating and installation instructions cona – ARI Armaturen CONA B PN630 EN User Manual
Page 13: B - bimetallic steam trap
Rev. 0040803000 4610
Page 13
Operating and installation instructions
CONA
®
B - Bimetallic steam trap
8.0 Troubleshooting
In the event of malfunction or faulty operating performance check that the installation and
adjustment work has been carried out and completed in accordance with these Operating
Instructions.
If malfunctions cannot be eliminate with the help of the following table
“9.0 Troubleshooting table”, the supplier or manufacturer should be consulted.
9.0 Troubleshooting table
-
ATTENTION !
- It is essential that the safety regulations are observed when identifying faults.
ATTENTION !
- refer to item 10.0 and 11.0 prior to dismantling and repair work!
- refer to item 6.0 before restarting the plant !
Fault
Possible cause
Corrective measures
No flow
Installed in wrong flow direction
Fit valve in direction of flow arrow.
Note installation position
Flange covers not removed
Remove flange covers
Little flow
Strainer clogged (pos. 2)
Clean / replace strainer;
refer to item 7.1
Piping system clogged
Check piping system
Wrong controller size choosen
Correct selection acc. to flow diagram
Changed upstream pressure or back
pressure operating conditions
Correct selection acc. to flow diagram
No closure, or internal
leakage
Controller clogged
Clean strainer and controller;
refer to item 7.1
Controller worn out
Replace controller; refer to item 7.1
Controller misadjusted/incorrectly set
Change setting; refer to item 5.3
Controller incorrectly screwed into body Check seal face between body and con-
troller, tighten controller correctly ; refer
to item 7.3
Controller operated above safe operating
pressure
Observe operating limits as per data
sheet, i.e. possibly select a different con-
troller
External leakage
Screw cap (pos. 6) or cover with hex. nut
(pos. 28) not properly tightened
Tighten; refer to item 7.3
Seal (pos. 26) defective