beautypg.com

Checking venting, Gas valves, Checking the input – State SBN85 390NE A User Manual

Page 25: Water temperature adjustment

background image

25

CheCking the input

For appliance installation locations with elevations above 2000

feet, refer to hIGh AlTITUDe INSTAllATIONS section of this

manual for input reduction procedure.
1. Attach a pressure gauge or a manometer to the manifold

pressure tap on the gas valve and refer to Table 3, for correct

manifold pressure.

2. Use this formula to “clock” the meter. Be sure that other gas

consuming appliances are not operating during this interval.

(3600/T) x h = Btuh
T = Time in seconds to burn one cubic foot of gas.
h = Btu’s per cubic foot of gas.
Btuh = Actual heater input.
example: (Using SBN100 250Ne heater)
T = 15.1 seconds
h = 1050 Btu
Btuh = ?
(3600/15.1) x 1050 = 250,000 (Compare with SBN100 250Ne

model and rating.)

Should it be necessary to adjust the gas pressure to the burners

to obtain the full input rate, the steps below should be followed:
3. remove the regulator adjustment sealing cap and adjust the pressure

by turning the adjusting screw with a screwdriver. See Figure 22.

Clockwise to increase gas pressure and input rate.

Counterclockwise to decrease gas pressure and input rate.

4. “Clock” the meter as in step 2 above.
5. repeat steps 3 and 4 until the specified input rate is achieved.
6. Turn the gas control knob to PIlOT. remove the pressure

gauge and replace the sealing cap and the Allen wrench set

screw in the pressure tap opening.

UNDer NO CIrCUMSTANCeS ShOUlD The GAS INPUT eXCeeD

The INPUT ShOWN ON The heATer MODel AND rATING PlATe.

OVerFIrING COUlD reSUlT IN DAMAGe Or SOOTING OF The heATer.

water temperature adjustment

Water temperature over 125°F (52°C)

can cause severe burns instantly

resulting in severe injury or death.
Children, the elderly and the

physically or mentally disabled are at

highest risk for scald injury.
Feel water before bathing or

showering.
Temperature limiting devices such as

mixing valves must be installed

when required by codes and to

ensure safe temperatures at fixtures.

The water temperature is controlled by a thermostat, Fig. 3,

which has two sensing elements. One sensor is located near the

top of the tank and the other is near the center. The thermostat

is set in the lowest position before the heater leaves the factory.
The thermostat temperature dial, Fig. 3, is accessible by

removing the control cover. The dial is adjustable and may be set

for 120°F (49°C) to 180°F (82°C) water temperature, but 120°F

(49°C) is the recommended starting point. It is suggested the dial

be placed on the lowest setting which produces an acceptable

hot water supply. This will always give the most energy efficient

operation. The temperature control has a 4°F fixed differential.

On multiple water heater installations the supply gas line regulators

shall be adjusted to provide gas pressure to each water heater

within the minimum and maximum supply pressure requirements

listed in Table 3 on page 8 with all gas fired appliances connected

to a common gas main firing at full capacity.
note: A pressure drop of more than 1.5” W. C. (0.37 kPa)

when the Main Burner ignites is an indication of an inadequate

supply of gas and can lead to ignition failure, rough starts and/

or rough operation. If a drop of more than 1.5” W. C. (0.37 kPa)

in supply gas pressure occurs when the Main Burner ignites,

ensure the supply gas lines and regulator(s) are properly sized

and installed. See the requirements for Supply Gas regulator

on page 12 and Gas Piping on page 23. ensure all requirements

and installation instructions are maintained.

CheCking Venting

The following steps shall be followed with each appliance connected

to the venting system placed in operation, while any other

appliances connected to the venting system are not in operation.
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch,

as required in the National Fuel Gas Code, ANSI Z223.1or

the CAN/CGA B149 Installation Codes and these instructions.

Determine that there is no blockage or restriction, leakage,

corrosion and other deficiencies which could cause an unsafe

condition.

3. So far as is practical, close all building doors and windows

and all doors between the space in which the water heater(s)

connected to the venting system are located and other spaces of

the building. Turn on all appliances not connected to the venting

system. Turn on all exhaust fans, such as range hoods and

bathroom exhausts, so they shall operate at maximum speed.

Close fireplace dampers.

4. Follow the lighting instruction. Place the water heater being

inspected in operation. Adjust thermostat so appliance shall

operate continuously.

5. Test for spillage at the burner level after 5 minutes of main

burner operation.

6. After it has been determined that each appliance connected

to the venting system properly vents when tested as outlined

above, return doors, windows, exhaust fans, fireplace dampers

and any other gas burning appliance to their previous conditions

of use.

7. If improper venting is observed during any of the above tests,

the venting system must be corrected.

FAIlUre TO COrreCT BACK DrAFTS MAy CAUSe AIr

CONTAMINATION AND UNSAFe CONDITIONS.
• If the back draft cannot be corrected by the normal method or

if a suitable draft cannot be obtained, a blower type flue gas

exhauster must be employed to assure proper venting and

correct combustion.

gas ValVes

Figure 22 shows the type of combination manual gas control valve

and regulator used on these heaters.
If the gas valve becomes defective, repairs should not be attempted.

A new valve should be installed in place of the defective one.

figure 22.