beautypg.com

Contaminated air, Air requirements, Contaminated air air requirements – State SBN85 390NE A User Manual

Page 14: Caution, Water damage hazard, Breathing hazard - carbon monoxide gas

background image

14

No valve or other obstruction is to be placed between the

Temperature-Pressure relief Valve and the tank. Do not connect

discharge piping directly to the drain unless a 6” (15.2 cm)

air gap is provided. To prevent bodily injury, hazard to life, or

property damage, the relief valve must be allowed to discharge

water in adequate quantities should circumstances demand. If

the discharge pipe is not connected to a drain or other suitable

means, the water flow may cause property damage.

Water Damage Hazard

Temperature-Pressure Relief Valve discharge

pipe must terminate at adequate drain.

CAUTION

t&p Valve discharge pipe requirements:

• Shall not be smaller in size than the outlet pipe size of the

valve, or have any reducing couplings or other restrictions.

• Shall not be plugged or blocked.
• Shall not be exposed to freezing temperatures.
• Shall be of material listed for hot water distribution.
• Shall be installed so as to allow complete drainage of both

the Temperature-Pressure relief Valve and the discharge

pipe.

• Must terminate a maximum of six inches above a floor

drain or external to the building. In cold climates, it is

recommended that the discharge pipe be terminated at an

adequate drain inside the building.

• Shall not have any valve or other obstruction between the

relief valve and the drain.

Burn hazard.

Hot water discharge.

Keep clear of Temperature-

Pressure Relief Valve

discharge outlet.

The Temperature-Pressure relief Valve must be manually

operated at least twice a year. Caution should be taken to ensure

that (1) no one is in front of or around the outlet of the Temperature-

Pressure relief Valve discharge line, and (2) the water manually

discharged will not cause any bodily injury or property damage

because the water may be extremely hot. If after manually

operating the valve, it fails to completely reset and continues to

release water, immediately close the cold water inlet to the water

heater, follow the draining instructions in this manual, and replace

the Temperature-Pressure relief Valve with a properly rated/sized

new one.
note: The purpose of a Temperature-Pressure relief Valve is

to prevent excessive temperatures and pressures in the storage

tank. The T&P valve is not intended for the constant relief of

thermal expansion. A properly sized thermal expansion tank must

be installed on all closed systems to control thermal expansion,

see Closed Water Systems and Thermal expansion on page 13.
If you do not understand these instructions or have any questions

regarding the Temperature-Pressure relief Valve call the toll

free number listed on the back cover of this manual for technical

assistance.

Contaminated air

Breathing Hazard - Carbon Monoxide Gas

Install water heater in accordance with

the Instruction Manual and NFPA 54 or

CAN/CSA-B149.1.
To avoid injury, combustion and ventilation

air must be taken from outdoors.
Do not place chemical vapor emitting

products near water heater.

Breathing carbon monoxide can cause brain damage or

death. Always read and understand instruction manual.

Corrosion of the flue ways and vent system may occur if air for

combustion contains certain chemical vapors. Such corrosion

may result in failure and risk of asphyxiation.
Combustion air that is contaminated can greatly diminish the life

span of the water heater and water heater components such as

hot surface igniters and burners. Propellants of aerosol sprays,

beauty shop supplies, water softener chemicals and chemicals

used in dry cleaning processes that are present in the combustion,

ventilation or ambient air can cause such damage.
Do not store products of this sort near the water heater. Air which

is brought in contact with the water heater should not contain any

of these chemicals. If necessary, uncontaminated air should be

obtained from remote or outdoor sources. The limited warranty

is voided when failure of water heater is due to a corrosive

atmosphere. (See limited warranty for complete terms and

conditions).

air reQuirements

Breathing Hazard - Carbon Monoxide Gas

Install water heater in accordance with

the Instruction Manual and NFPA 54 or

CAN/CSA-B149.1.
To avoid injury, combustion and ventilation

air must be taken from outdoors.
Do not place chemical vapor emitting

products near water heater.

Breathing carbon monoxide can cause brain damage or

death. Always read and understand instruction manual.

For safe operation an adequate supply of fresh uncontaminated

air for combustion and ventilation must be provided.
An insufficient supply of air can cause recirculation of combustion

products resulting in contamination that may be hazardous to

life. Such a condition often will result in a yellow, luminous burner

flame, causing sooting of the combustion chamber, burners and

flue tubes and creates a risk of asphyxiation.
Do not install the water heater in a confined space unless an

adequate supply of air for combustion and ventilation is brought

in to that space using the methods described in the Confined

Space section that follows.