When ducts are used, they shall be of the same cross sectional

area as the free area of the openings to which they connect.

The minimum dimension of rectangular air ducts shall be not less

than 3 inches.

air from other indoor spaCes

figure 18.

The confined space shall be provided with two permanent

openings, one commencing within 12 inches (300 mm) of the top

and one commencing within 12 inches (300 mm) of the bottom of

the enclosure. See Figure 18.
each opening shall communicate directly with an additional

room(s) of sufficient volume so that the combined volume of all

spaces meets the criteria for an Unconfined Space.
each opening shall have a minimum free area of 1 square inch

per 1,000 Btu/hr (2200 mm

2

per kW) of the aggregate input rating

of all appliances installed in the enclosure. each opening shall

not be less than 100 square inches (645 cm

2

).

outdoor air through two VertiCal duCts

The illustrations shown in this section of the manual are a

reference for the openings that provide fresh air into confined

spaces only.
do not refer to these illustrations for the purpose of vent

installation. See Venting Installation on page 15 for complete

venting installation instructions.

figure 17.

The confined space shall be provided with two permanent vertical

ducts, one commencing within 12 inches (300 mm) of the top and

one commencing within 12 inches (300 mm) of the bottom of the

enclosure. The vertical ducts shall communicate directly with the

outdoors. See Figure 17.

each duct opening shall have a minimum free area of 1 square

inch per 4,000 Btu/hr (550 mm

2

per kW) of the aggregate input

rating of all appliances installed in the enclosure.