beautypg.com

Sequence of operation chart – State GS6 40 YBFS User Manual

Page 33

background image

33

SEQUENCE OF OPERATION CHART

Apply Power
to Appliance.

Is Damper

Closed?

Y

Is there a

Call for Heat.

Is Damper

Open?

Will not attempt to light. 2
flash error code. See
Corrective Action Table
on pages 31-32.

N

Damper Energizes.

Gas Valve attempts to open damper
for 30 seconds, displays 3 flash error
code, and then waits 2 mintues before
attempting to open damper again. See
Corrective Action Table pages 31-32.

N

Pilot Valve

Energizes

Does Pilot

Valve Open?

Spark Electrode

is Energized

Is

Pilot Flame

Sensed Within

1.5 min. ?

Main Valve

Energized

Does Main

Valve Open?

Is Main

Flame Sensed?

Is Demand for

Heat Satisfied?

Pilot & Main

Valve De-Energize.

Is Flame

Sensed?

Damper Energizes

and Closes.

Will not light. 8-4 flash
error code. See Corrective
Action Table on pages 31-32.

N

Will not light. 8-4 flash
error code. See Corrective
Action Table on pages 31-32.

N

Will not light. 8-4 flash
error code. See Corrective
Action Table on pages 31-32.

N

Will not light. 8-4 flash
error code. See Corrective
Action Table on pages 31-32.

N

Water heater will continue to
operate normally until
demand is satisfied.

N

Wait for flame lost, 5 flash
error code. See Corrective
Action Table, pages 31-32.

Y

Damper closes, displays 6-4
Flash Error Code, and gas
control valve goes into 20
minute lockout. See Corrective
Action Table, pages 31-32.

This manual is related to the following products: