Mezzanine connector definitions, System maintenance switch, System maintenance switch procedures – HP ProLiant BL465c G7 Server-Blade User Manual
Page 10: Clearing the system configuration

Component identification 10
Mezzanine connector definitions
Item
PCIe
Mezzanine connector 1
x8, Type I mezzanine card only
Mezzanine connector 2
x8, Type I or II mezzanine card
System maintenance switch
Position
Function
Default
1*
iLO 3 security override
Off
2
Configuration lock
Off
3
Reserved
Off
4
Reserved
Off
5*
Password disabled
Off
6*
Reset configuration
Off
7
Reserved
Off
8
Reserved
Off
9
Reserved
Off
10
Reserved
Off
*To access redundant ROM, set S1, S5, and S6 to ON.
System maintenance switch procedures
When you perform troubleshooting steps, this guide may instruct you to perform the following procedures:
•
Clear the system configuration ("
Clearing the system configuration
" on page
•
Access the redundant ROM ("
" on page
To complete these procedures, you must change physical settings on the system maintenance switch.
Clearing the system configuration
RBSU can be used to restore the factory default configuration. For more information, see "HP ROM-Based
Setup Utility (on page
)." If the system is unable to boot into RBSU, use the following steps to clear the
system configuration:
1.
Power down the server blade (on page
2.
Remove the server blade (on page
3.
Remove the access panel (on page
4.
Change position 6 of the system maintenance switch to on.
5.
Install the access panel (on page
6.
Install the server blade in the enclosure and power up the server blade.
7.
Wait for the POST message that prompts you to change the switch setting:
Maintenance switch detected in the "On" position.
Power off the server and turn switch to the "Off" position.