Component identification 10

Mezzanine connector definitions

Item

PCIe

Mezzanine connector 1

x8, Type I mezzanine card only

Mezzanine connector 2

x8, Type I or II mezzanine card

System maintenance switch

Position

Function

Default

1*

iLO 3 security override

Off

2

Configuration lock

Off

3

Reserved

Off

4

Reserved

Off

5*

Password disabled

Off

6*

Reset configuration

Off

7

Reserved

Off

8

Reserved

Off

9

Reserved

Off

10

Reserved

Off

*To access redundant ROM, set S1, S5, and S6 to ON.

System maintenance switch procedures

When you perform troubleshooting steps, this guide may instruct you to perform the following procedures:

Clear the system configuration ("

Clearing the system configuration

" on page

10

).

Access the redundant ROM ("

Accessing the redundant ROM

" on page

11

).

To complete these procedures, you must change physical settings on the system maintenance switch.

Clearing the system configuration

RBSU can be used to restore the factory default configuration. For more information, see "HP ROM-Based
Setup Utility (on page

50

)." If the system is unable to boot into RBSU, use the following steps to clear the

system configuration:

1.

Power down the server blade (on page

13

).

2.

Remove the server blade (on page

14

).

3.

Remove the access panel (on page

15

).

4.

Change position 6 of the system maintenance switch to on.

5.

Install the access panel (on page

15

).

6.

Install the server blade in the enclosure and power up the server blade.

7.

Wait for the POST message that prompts you to change the switch setting:
Maintenance switch detected in the "On" position.
Power off the server and turn switch to the "Off" position.