beautypg.com

Troubleshooting flowchart, Heat pump running... but is it heating, Start – Aquacal 110 User Manual

Page 28: Problem solved. problem solved

background image

28

TROUBLESHOOTING FLOWCHART

START

Is the air being discharged

out of the top of the heater 9-12

degrees cooler than the

outside air?

START

Is the air being discharged

out of the top of the heater 9-12

degrees cooler than the

outside air?

Is the pool pump timer
set to allow extended

operation of the heater?

Is the pool pump timer
set to allow extended

operation of the heater?

Yes

Extend the pool pump's

hours of operation to

accommodate

additional heater run

time required in cooler

conditions.

Extend the pool pump's

hours of operation to

accommodate

additional heater run

time required in cooler

conditions.

Is the heater

perf orming

adequately ?

Is the heater

perf orming

adequately ?

Problem

Solved.

Problem

Solved.

No

Yes

Does the display read : "FS" ?

Does the display read : "FS" ?

No

Yes

HEAT ONLY MODELS: "FS"

display ed indicates air

temperature may be too low to

support the heater's

operation. Heater will remain in

def rost until air temperature

rises.

HEAT-COOL MODELS:"FS"

indicates heater is def rosting.

HEAT ONLY MODELS: "FS"

display ed indicates air

temperature may be too low to

support the heater's

operation. Heater will remain in

def rost until air temperature

rises.

HEAT-COOL MODELS:"FS"

indicates heater is def rosting.

Call AquaCal

for Assistance:

800-786-7751.

Call AquaCal

for Assistance:

800-786-7751.

No

Yes

No

Yes

No

Problem

Solved.

Problem

Solved.

HEAT ONLY MODELS: Ambient

conditions too cold to operate

heater.

HEAT-COOL MODELS: "FS"

display ed f or 5-minutes or less

indicates normal def rost

operation.

HEAT ONLY MODELS: Ambient

conditions too cold to operate

heater.

HEAT-COOL MODELS: "FS"

display ed f or 5-minutes or less

indicates normal def rost

operation.

HEAT ONLY MODELS: Has the air

temperature remained abov e

38ºF f or sev eral hours and "FS"

has been display ed throughout

the period?

HEAT-COOL MODELS: Has "FS"

remained display ed longer than

5-minutes (If y es, shut heater

of f .)?

HEAT ONLY MODELS: Has the air

temperature remained abov e

38ºF f or sev eral hours and "FS"

has been display ed throughout

the period?

HEAT-COOL MODELS: Has "FS"

remained display ed longer than

5-minutes (If y es, shut heater

of f .)?

Heat Pump Running... but is it Heating?

(Assumes Heating Indicator Light is Illuminated)

This manual is related to the following products: