Water Inc wi-hp9100-TS Upflou User Manual
Page 3

Water Pressure
A minimum of 25 pounds of water pressure is required for
regeneration valve to operate effectively.
Electrical Facilities
A continuous 115 volt, 60 Hertz current supply is required.
Make certain the current supply is always hot and cannot be
turned off with another switch.
Existing Plumbing
Condition of existing plumbing should be free from lime and
iron buildup. Piping that is built up heavily with lime and/or iron
should be replaced. If piping is clogged with iron, a separate
iron filter unit should be installed ahead of the water softener.
Location Of Softener And Drain
The softener should be located close to a drain.
Bypass Valves
Always provide for the installation of a bypass valve.
Tank and Probe Assembly
Use only 100% silicone lubricant on the probe O-rings
(Figure 2). Do not allow the lubricant to come into contact with
the probe pins. Install the probe assemblies into the tank and
secure with the locking clasp (Figure 3).
Important: The pins on the probes will only fit into the bulkhead
fittings one way. The pins must go into the matching holes at
the bottom of the fitting. The probe with the shortest length of
wire must be on top. Install the protective shield (Figure 3).
NOTE: Do not attempt to tighten or loosen the Bulkhead
fittings as they are secured with a locking
adhesive.
Lubricate
Probe Pins
Figure 2
Locking Clasp
Bulkhead Fitting
Protective
Shield
Figure 3
GENERAL AND COMMERCIAL
INSTALLATION INSTRUCTIONS
continued
Valve to Tank Installation Instructions
1. Spin the valve onto the tank, ensuring the threads are not
cross-threaded.
NOTE: All Fleck® valves are right-hand threads, or
clockwise, to install.
2. Rotate the valve freely without using force until it comes to
a stop (this position is considered zero).
3. Rotate the valve clockwise from zero, between ¼ turn and
½ turn (Figure 4).
Figure 4
NOTE: If lubricant is required, a silicone compound
is strongly recommended. Dow Corning®
Silicone Compound (available from Fleck®), is
recommended for best possible results. Dow
Corning® 7 Release Compound is used in the
manufacture of Fleck® control valves. The use of
other types of lubricants may attack the control’s
plastic or rubber components. Petroleum-based
lubricants can cause swelling in rubber parts,
including O-rings and seals.
Part No.
Description
16174
Silicone, 2 oz Tube
16586-8
Silicone, Dow #7 8 LB
WARNING:
Do not exceed water pressure of 125 psi
(8.6 bar). Do not exceed 110°F (43.3°C). Do
not subject unit to freezing conditions.
9100 TS Control Operation
Power Loss Memory Retention
The 9100 TS control features battery-free Time of Day and
Day of Week retention during temporary loss of power. A super
capacitor is designed to keep time for 8 to 24 hours depending
on the installation. If the super capacitor is exhausted the 9100
TS control will display four dashes (- - : - - ) immediately upon
power up. The Time of Day and Day of Week must be reset.
All other programmed parameters are stored in the static
memory and are retained.
9100 TS Upflow JA11 • 3