beautypg.com

Allied Air Enterprises A95DF User Manual

Page 28

background image

506725-01

Page 28 of 48

Issue 1109

Gas Piping

1. Gas piping may be routed into the unit through either

the left or right hand side. Supply piping enters into

the gas valve from the side of the valve as shown in

Figure 43. Move bellows grommet to side of the cabinet

which the gas line enters. Ensure opposite gas line

entrance is plugged with supplied plug.

A low inlet pressure switch in LP/propane applications

is recommended.

IMPORTANT

Do Not exceed 600 in. lbs. (50 ft. lbs.) torque when

attaching the gas piping to the gas valve.

WARNING

If a flexible gas connector is required or allowed by the

authority that thas jurisdiction, black iron pipe shall be

installed at the gas valve and extend outside the furnace

cabinet. The flexible connector can then be added

between the black iron pipe and the gas supply line.

CAUTION

2. When connecting gas supply, factors such as length of

run, number of fittings and furnace rating must be
considered to avoid excessive pressure drop. Table 10

lists recommended pipe sizes for typical applications.

NOTE: Use two wrenches when connecting gas piping to
avoid transferring torque to the manifold.

3. Gas piping must not run in or through air ducts, clothes

chutes, chimneys or gas vents, dumb waiters or elevator
shafts. Center gas line through piping hole. Gas line
should not touch side of unit. See Figures 43.

4. Piping should be sloped 1/4 inch per 15 feet (6 mm per

5.6 m) upward toward the gas meter from the furnace.
The piping must be supported at proper intervals, every

8 to 10 feet (2.44 to 3.05 m), using suitable hangers or
straps. Install a drip leg in vertical pipe runs to serve as
a trap for sediment or condensate.

5. A 1/8" N.P.T. plugged tap or pressure post is located on

the gas valve to facilitate test gauge connection. See
Figure 50.

6. In some localities, codes may require installation of a

manual main shut off valve and union (furnished by
installer) external to the unit. Union must be of the
ground joint type.

Leak Check

After gas piping is completed, carefully check all piping

connections (factory and field installed) for gas leaks. Use

a leak detecting solution or other preferred means.

The furnace must be isolated from the gas supply system

by closing its individual manual shut off valve during any

pressure testing of the gas supply system at pressures

greater than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).

Compounds used on threaded joints of gas piping must

be resistant to the actions of liquified petroleum gases.

IMPORTANT

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result

in serious injury, death, or property damage. Never use

an open flame to test for gas leaks. Check all

connections using a commercially available soap

solution made specifically for leak detection. Some

soaps used for leak detection are corrosive to certain

metals. Carefully rinse piping thoroughly after leak test

has been completed.

WARNING

When testing pressure of gas lines, gas valve must be

disconnected and isolated. (See Figure 42.) Gas

Valves can be damaged if subjected to pressures

greater than 1/2 psig (3.48 kPa).

IMPORTANT

FIGURE 42

MANUAL MAIN SHUT−OFF

VALVE WILL NOT HOLD

NORMAL TEST PRESSURE

CAP

FURNACE

ISOLATE

GAS VALVE

1/8" N.P.T. PLUGGED TAP

This manual is related to the following products: