Do Not use copper tubing or existing copper condensate

lines for drain line.

CAUTION

Condensate Piping

This unit is designed for either right or left side exit of

condensate piping in downflow applications. Refer to

Figure 38 for condensate trap locations.
NOTE: If necessary the condensate trap may be installed

up to 5” away using PVC pipe from the furnace. Piping from

furnace must slope down a minimum of 1/4” per ft. toward

trap.

1. Determine which side condensate piping will exit the

unit, location of trap, field-provided fittings and length of

PVC pipe required to reach available drain.

2. Remove plug (Figure 38) from the cold end header box

at the appropriate location on the side of the unit. Install

field-provided 1/2 NPT male fitting into cold end header

box. Use Teflon tape or appropriate pipe dope.

3. Install the cap over the clean out opening at the base of

the trap. Secure with clamp. See Figure 41.

4. Install drain trap using appropriate PVC fittings, glue all

joints. Glue the provided drain trap as shown in

Figure 41. Route the condensate line to an open drain.

Condensate line must maintain a 1/4” downward slope

from the furnace to the drain.

5. If unit will be started immediately upon completion of

installation, prime trap per procedure outlined in Unit

Start-Up section.

FIGURE 39

CONDENSATE TRAP LOCATION

(shown with right side exit of condensation)

5’ max.

to drain

Field Provided Vent

min. 1" Above

Condensate Drain

1" min.

Trap can be installed a

maximum of 5 ft. from furnace.

(*PVC Only)

*Piping from furnace must slope down a minimum of
1/4" per ft. toward trap.

FIGURE 40

UNIT WITH EVAPORATOR COIL

Drain

Condensate trap and

evaporator coil must drain

separately as shown.

Field−Provided Vent

A separate drain line must be run to the drain from the

condensate trap to ensure proper drainage and pressure

switch operation. DO NOT connect the condensate trap

drain into the drain line from the evaporator coil.

CAUTION

FIGURE 38

CONDENSATE TRAP AND PLUG LOCATIONS

Trap

(same on

right side)

Plug

(same on left

side)

1−1/2 in.

Condensate line must slope downward away from the trap

to drain. If drain level is above condensate trap, condensate

pump must be used. Condensate drain line should be routed

within the conditioned space to avoid freezing of condensate

and blockage of drain line. If this is not possible, a heat

cable kit may be used on the condensate trap and line.

Heating cable kit is available in various lengths:

6 ft. (1.8 m) - kit no. 26K68; 24 ft. (7.3 m) - kit no. 26K69;

and 50 ft. (15.2 m) - kit no. 26K70.