Details of Exhaust Piping Terminations for Non-Direct

Vent Applications

Exhaust pipe may be routed either horizontally through an

outside wall or vertically through the roof. In attic or closet

installations, vertical termination through the roof is preferred.

Figures 34 through 37 show typical terminations.

1. Exhaust piping must terminate straight out or up as

shown. The termination pipe must be sized as listed in

Table 8. The specified pipe size ensures proper velocity

required to move the exhaust gases away from the

building.

2. On field supplied terminations for side wall exit, exhaust

piping may extend a maximum of 12 inches (305 mm)

for 2” PVC and 20” (508 mm) for 3” (76 mm) PVC beyond

the outside wall. See Figure 35.

3. If exhaust piping must be run up a sidewall to position

above snow accumulation or other obstructions, piping

must be supported every 24” (610 mm) as shown in

Figure 36. When exhaust piping must be run up an

outside wall, any reduction in exhaust pipe size must be

done after the final elbow.

FIGURE 34

NON−DIRECT VENT ROOF TERMINATION KIT

(15F75 or 44J41)

UNCONDITIONED

ATTIC SPACE

3" (76mm) OR

2" (51mm) PVC

PROVIDE SUPPORT

FOR EXHAUST LINES

12" (305mm)

ABOVE AVE.

SNOW

ACCUMULATION

SIZE TERMINATION

PIPE PER TABLE 8.

1/2" (13mm) FOAM

INSULATION IF REQUIRED

FIGURE 35

1/2" (13mm) ARMAFLEX

INSULATION IN

UNCONDITIONED SPACE (IF REQUIRED)

PVC REDUCER

1/2" (13mm)

ARMAFLEX

INSULATION

NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION

SIZE TERMINATION

PIPE PER TABLE 8.

FIELD−PROVIDED

REDUCER MAY

BE REQUIRED TO

ADAPT LARGER

VENT PIPE SIZE

TO TERMINATION

12" MIN.

(305mm)

Above Grade or

average snow

accumulation

12" (305mm) MAX. for 2" (51mm)
20" (508mm) MAX. for 3" (76mm)

(IF REQUIRED)

FIGURE 36

12" (305mm)

ABOVE GRADE OR

AVERAGE SNOW

ACCUMULATION

UNCONDITIONED

SPACE

1/2" (13mm) FOAM

INSULATION (IF REQUIRED)

1/2" (13mm) FOAM

INSULATION IN

UNCONDITIONED

SPACE (IF REQUIRED)

*WALL SUPPORT

OUTSIDE WALL

SIZE TER-
MINATION

PIPE PER

TABLE 8.

FIELD−PROVIDED

REDUCER MAY BE

REQUIRED TO

ADAPT LARGER

VENT PIPE SIZE TO

TERMINATION

*Use wall support every 24" (610). Use two supports if extension is

greater than 24" but less than 48".

12" (305mm) MAX. for 2" (51mm)
20" (508mm) MAX. for 3" (76mm)

NON−DIRECT VENT FIELD SUPPLIED WALL

6" (152mm)

Max

TERMINATION EXTENDED

NOTE − Do not discharge exhaust gases directly into any chimney or vent st ack. If ver-
tical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illus-
trated. In any exterior portion of chimney, the exhaust vent must be insulated.

FIGURE 37

STRAIGHT−CUT OR

ANGLE−CUT IN DIRECTION

OF ROOF SLOPE

EXHAUST VENT

1/2" (13mm)

WEATHERPROOF

INSULATION (IF REQUIRED)

SHOULDER OF FITTINGS

PROVIDE SUPPORT

OF PIPE ON TOP PLATE

EXTERIOR

PORTION OF

CHIMNEY

INSULATE

TO FORM

SEAL

SHEET

METAL TOP

PLATE

SIZE TERMINATION

PIPE PER TABLE 8.

NON−DIRECT VENT APPLICATION

USING EXISTING CHIMNEY

Minimum 12" (305MM)

above chimney top

plate or average snow

accumulation