beautypg.com

Allied Air Enterprises A95DF User Manual

Page 15

background image

506725-01

Page 15 of 48

Issue 1109

Vent Piping Guidelines

This gas furnace can be installed as either a Non-Direct

Vent or a Direct Vent gas central furnace.

NOTE: In non-Direct Vent installations, combustion air is

taken from indoors and flue gases are discharged outdoors.

In Direct Vent installations, combustion air is taken from

outdoors and flue gases are discharged outdoors.

Intake and exhaust pipe sizing - Size pipe according to Tables

6 and 7. Table 6 lists the minimum vent pipe lengths

permitted. Table 7 lists the maximum pipe lengths permitted.

Regardless of the diameter of pipe used, the standard roof

and wall terminations described in section Exhaust Piping

Terminations should be used. Exhaust vent termination pipe

is sized to optimize the velocity of the exhaust gas as it exits

the termination.

In some applications which permit the use of several different

sizes of vent pipe, a combination vent pipe may be used.

Contact Allied Air Technical Service for assistance in sizing

vent pipe in these applications.

1. In areas where piping penetrates joist or interior walls,

hole must be large enough to allow clearance on all

sides of pipe through center of hole using a hanger.

2. When furnace is installed in a residence where unit is

shut down for an extended period of time, such as a

vacation home, make provisions for draining condensate

collection trap and lines.

Exhaust Piping (Figure 20)

Route piping to outside of structure. Continue with

installation following instructions given in piping termination

section.

The exhaust vent pipe operates under positive pressure

and must be completely sealed to prevent leakage of

combustion products into the living space.

CAUTION

Do not discharge exhaust into an existing stack or stack

that also serves another gas appliance. If vertical

discharge through an existing unused stack is required,

insert PVC pipe inside the stack until the end is even

with the top or outlet end of the metal stack.

CAUTION

Do not use screens or perforated metal in exhaust or

intake terminations. Doing so will cause freeze-ups and

may block the terminations.

IMPORTANT

TABLE 6

MINIMUM VENT PIPE LENGTHS

A95DF, 95G1DF, A93DF, & 92G1DF

MODELS

MIN. VENT LENGTH*

045, 070, 090, 110

15 ft. or

5 ft plus 2 elbows or

10 ft plus 1 elbow

*Any approved termination may be added to the minimum length listed.

Use the following steps to correctly size vent pipe diameter.

1

2

3

4

5

6

045, 070,
090, 110

Which termination?

Standard or
Concentric?

See Table 5

Intake or

exhaust

Which needs
most elbows?

How many?

2", 2 1/2"

or 3"

Desired pipe size?

Use Table 7 to find
max intake or exhaust
pipe length.

FIGURE 19

What is the altitude?

7

Furnace capacity?

This manual is related to the following products: