Technical data
• Nominal voltage: 230–240 V~, +10 %/-15 %
• Frequency:
50-60 Hz
• Power consumption: max. 6 VA
• Switching output: phase-independent
(zero-crossover switching),
• TR 611 top2:
suitable for switching SELV
(Safe Extra-Low Voltage)
• Contact:
two way switch
• Contact material: AgSnO
2
• Switching capacity max.: 16 A, 250 V~, cos ϕ = 1;
10 A, 250 V~, cos ϕ = 0.6
• Switching capacity min.: 10 mA/230 V AC
100 mA/24 V AC/DC
• Incandescent lamp load:
2600 W
• Halogen lamp load:
2600 W
• Fluorescent lamp load: uncorrected:
1000 VA series corrected
730 VA (80 μF) parallel corrected
• Compact fluorescent lamps: 22 x 7 W, 18 x 11 W
16 x 16 W, 20 x 14 W, 23 x 15 W,
• Permissible ambient temperature: –30 °C ... +55 °C
• Protection class: II in accordance with
EN 60730-1 for designated installation
• Protection rating: IP 20 in accordance with
EN 60529
• Pollution level:
2
• Power consumption: 10 years at 20 °C