beautypg.com

Tower water reservoir, Cooling tower – Sterlco SF Series Cooling Towers User Manual

Page 14

background image

Fiberglass Cooling Towers

Chapter 3: Installation

Page 14 of 25

Install the piping according to the piping diagrams in Figure 3 on page 14, Figure 4 on page
14, and Figure 5 on page 15.

Figure 3: Cooling Tower with Tower Reservoir Piping Diagram

inlet

Type 2

Type 2

pressure

gauge

Do not apply

excessive torque

to fittings

Caution!

Overflow

3/4" constant

bleed

Drain

To drain

Strainer basket

Tower water

reservoir

TR

Cooling tower

T

Type 2

balancing

valve

TWR

TWR

Typical bottom outlet

Makeup

P-1

P

Drain line is intended to prevent
tower freeze-up. Do not valve.

NOTE:

Support piping to eliminate
load from tower casing

Bypass

Tower water return
Tower water supply

City water

TWS

TWS

TWR

3/4" constant bleed

3/8" drain line

P

Figure 4: Cooling Tower with Basin as Reservoir Piping Diagram

Pressure

gauge

P

Overflow

Caution!

Do not apply

excessive torque

to fittings

Support piping to eliminate

load from tower casing

To drain

TR

Cooling

tower

TR

TWR

City water line

TWR
TWS

TWS

To drain

P-1

P

Inlet
Balancing valve

Makeup

Side outlet

Drain

Building

exterior

Thermostat-mount

in piping (1/2" fitting)

3/4" constant bleed

1/4" swing check valve

12" above highest point

in return line

Bypass

Tower water return
Tower water supply

City water