Chapter 3: Installation
3-1 Location
Mount the instrument in a location that will not be subject to excessive temperature, shock or 
vibration. All models are designed for mounting in an enclosed panel. 
When properly mounted in an enclosed panel using a gasket at the panel/controller interface, 
the keypad can be washed down with water. Do not use high-pressure fluids. 
3-2 Electrical Connections
Microprocessor-based instruments require a “clean” source of power that is steady and free of 
noise. Electrical noise may be caused by line faults, power switching, motors, motor 
controllers, or power controllers containing SCR devices. Without a clean source, any 
microprocessor is prone to failure. If your power source is not from a clean line, your system 
can be protected by installing a line filter. 
Where external contactors or solenoids are used with relay output instruments, an R/C 
Snubber Network should be used. The snubber installs easily directly across the field coil 
terminals of the relay or solenoid. 
Do not run thermocouples, RTD’s or other class 2 wiring in the same conduit or area as the 
power leads. Maintain separation between wiring of sensors, process signals and other power 
and control wiring. 