CONTROLLER STATUS
POLL:
31 44
SELECT:
N/A
FORMAT:
Status
UNITS:
None
DESCRIPTION:
Instrument status.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
N/A
N/A
Manual Control
Low Alarm 1
High Alarm 1
N/A
N/A
Open TC Alarm
N/A
Shorted TC Alarm
N/A
N/A
N/A
N/A
N/A
Process
Out
of
Cont.
PROCESSING
BIT#:
0
DESCRIPTION:
This status bit states whether this unit is currently processing.
0 = not currently processing (3200 manual mode)
1 = processing (3200 auto mode)
MANUAL CONTROL
BIT#:
2
DESCRIPTION:
Indicates if the control is in manual (open loop) or automatic (closed loop) control.
0 = Automatic Control
1 = Manual Control (or standby)
LOW ALARM 1
BIT#
3
DESCRIPTION:
Indicates that the first configured 3200 alarm is active. For example if Alarm 1 is not configured and Alarm 2
is set to be an absolute low alarm, this bit will be set if the temperature is lower than alarm setpoint 2.
HIGH ALARM 2
BIT#
4