beautypg.com

1 master parameter list, Master parameter list – Sterlco SMC 2-3.5 Portable Chillers User Manual

Page 13

background image

3200 Series

ACS 3216 Operators Manual 13

7.1.1

Master Parameter List

INPUT LIST

I N P U T

Name

Scrolling Display

Parameter Description

Value

Default

Access Level

I N . T Y P

INPUT TYPE

Selects input linearisation and range

See manufacture manual for input types available

Conf

L3 R/O

none

No units - only for custom linearisation

o

C

Celsius

o

F

Fahrenheit

o

k

Kelvin

U N I T S

DISPLAY UNITS

Display units shown on the
instrument

PErc

%

o

C

L3

nnnn

No DP

nnn.n

One DP

D E C . P

DISPLAY
POINTS

Decimal point position

nn.nn

Two DP

nnnn

Conf

L3 R/O

M V . H I

LINEAR INPUT
HIGH

High limit for mV (mA) inputs

-10.00 to +80.00mV

80.00

Conf

M V . L o

LINEAR INPUT
LOW

Low limit for mV (mA) inputs

-10.00 to +80.00mV

-10.00 Conf

RNG.HI

RANGE HIGH
LIMIT

Range high limit for thermocouple
RTD and mV inputs

From the high limit of the selected input type to the
‘Low Range Limit’ parameter minus one display unit.

Conf

L3 R/O

RNG.LO

RANGE LOW
LIMIT

Range low limit for thermocouple
RTD and mV inputs

From the low limit of the selected input type to the
‘High Range Limit’ parameter minus one display unit.

Conf

L3 R/O

PV.OFS

PV OFFSET

A simple offset applied to all input
values.

Generally one decimal point more than PV

L3

F I L T . T

FILTER TIME

Input filter time

OFF to 100.0 seconds

1.6

L3

Auto

Automatic

0

o

C

Fixed at 0

o

C

C J . t y p

CJC TYPE

Configuration of the CJC type

50

o

C

Fixed at 50

o

C

Auto

Conf and if
T/C

L3 R/O

oFF

No sensor break will be detected

on

Open circuit sensor will be detected

S B . t y p

SENSOR BREAK
TYPE

Defines the action which is applied
to the control output if the sensor
breaks (open circuit).

Lat

Latching

on

Conf

L3 R/O

C J C . i n

CJC
TEMPERATURE

Temperature measured at the rear
terminal block. Used in the CJC
calculation

Read only

Conf

L3 R/O and
if T/C

P v . i n

PV INPUT
VALUE

Current measured temperature

Minimum display to maximum display range

Conf

L3 R/O

m v . i n

MILLIVOLT
INPUT VALUE

Millivolts measured at the rear PV
Input terminals

xx.xx mV - read only

Conf

L3 R/O

INPUT/OUTPUT LIST 1 ‘I O -1 ’

Name

Scrolling Display

Parameter Description

Value

Default

Access Level

none

No input or output fitted

dC.OP

DC output

ReLy

Relay output

L.IO

Logic Input/Output

1..i d

I/O 1 TYPE

I/O channel 1 hardware type
defined by the hardware
fitted

SSR

Triac output

As
ordered

Read only

none

Disabled. If disabled no further
parameters are shown

d.out

Digital output

UP

Valve open codes VC and VP only

dwn

Valve close codes VC and VP only

Heat

Heat output

CooL

Cool output

d.in

Digital input if ‘1.i d ’ = ‘

L.IO

HEAt

Conf

w.SP

Working setpoint re-transmission

PV

Process variable re-transmission

1.FUNC

I/O 1 FUNCTION

I/O channel function.

If the instrument is ordered
as valve positioner (codes
VC or VP), only options
available are ,

none,

d.out, UP, or dwn

Note: If output 1 is set to
Up ensure the other valve
position output is set to
dwn and vice versa

OP

Output power demand re-transmission

Shown if I/O 1 TYPE =
dc.OP Retransmission