3 modbus parameter addresses, Modbus parameter addresses – Sterlco SMC 2-3.5 Portable Chillers User Manual

Page 24

background image

3200

Series

24 ACS 3216 Operators Manual

9.3

Modbus Parameter Addresses

Parameter
Mnemonic

Parameter Name

Modbus Address

PV.IN

PV (Temperature) Input Value (see also Modbus address 203 which allows writes over Modbus to this variable).

1

TG.SP Target

Setpoint.

NB – do not write continuously changing values to this variable. The memory technology used in this product has a
limited (100,000) number of write cycles. If ramped setpoints are required, consider using the internal ramp rate function
or the remote comms setpoint (Modbus address 26 )in preference.

2

MAN.OP

Manual Output Value

3

WRK.OP Working

Output

4

WKG.SP

Working Setpoint (Read Only)

5

PB Proportional

Band

6

Ti Integral

Time

(0 = No Integral Action)

8

Td Derivative

Time

(0 = No Derivative Action)

9

A1.---

Alarm 1 Threshold

13

A2.---

Alarm 2 Threshold

14

T.STAT

Timer Status

0 = Reset

1 = Run

2 = Hold

3 = End

23

SP1

Setpoint 1

NB – do not write continuously changing values to this variable. The memory technology used in this product has a
limited (100,000) number of write cycles. If ramped setpoints are required, consider using the internal ramp rate function
or the remote comms setpoint (Modbus address 26 )in preference.

24

SP2

Setpoint 2

NB – do not write continuously changing values to this variable. The memory technology used in this product has a
limited (100,000) number of write cycles. If ramped setpoints are required, consider using the internal ramp rate function
or the remote comms setpoint (Modbus address 26 )in preference.

25

OP.HI

Output High Limit

30

OP.LO

Output Low Limit

31

SP.RAT

Setpoint Rate Limit Value (0 = no rate limit)

35

StAt

Instrument Status. This is a bitmap:

B0 – Alarm 1 Status

B1 – Alarm 2 Status

B2 – Alarm 3 Status

B3 – Alarm 4 Status

B4 – Auto/Manual Status

B5 – Sensor Break Status

B6 – Loop Break Status

B7 – CT Low load current alarm status

B8 – CT High leakage current alarm status

B9 – Program End

B10 – PV Overrange (by > 5% of span)

B11 – CT Overcurrent alarm status

B12 – New Alarm Status

B13 – Timer/Ramp Running

B14 – Remote (comms) SP Fail

B15 – Autotune Status

In each case, a setting of 1 signifies ‘Active’, 0 signifies ‘Inactive’.

75

A3.---

Alarm 3 Threshold

81

A4.---

Alarm 4 Threshold

82

Home

Home Display.

0 – Standard PV and SP display

1 – PV and Output Power display

2 – PV and Time remaining display

3 – PV and Timer elapsed time display

4 – PV and Alarm 1 setpoint

5 – PV and Load Current

6 – PV only

7 – PV and Composite SP/Time remaining

106