3 modbus parameter addresses, Modbus parameter addresses – Sterlco SMC 2-3.5 Portable Chillers User Manual
Page 24
3200
Series
24 ACS 3216 Operators Manual
9.3
Modbus Parameter Addresses
Parameter
Mnemonic
Parameter Name
Modbus Address
PV.IN
PV (Temperature) Input Value (see also Modbus address 203 which allows writes over Modbus to this variable).
1
TG.SP Target
Setpoint.
NB – do not write continuously changing values to this variable. The memory technology used in this product has a
limited (100,000) number of write cycles. If ramped setpoints are required, consider using the internal ramp rate function
or the remote comms setpoint (Modbus address 26 )in preference.
2
MAN.OP
Manual Output Value
3
WRK.OP Working
Output
4
WKG.SP
Working Setpoint (Read Only)
5
PB Proportional
Band
6
Ti Integral
Time
(0 = No Integral Action)
8
Td Derivative
Time
(0 = No Derivative Action)
9
A1.---
Alarm 1 Threshold
13
A2.---
Alarm 2 Threshold
14
T.STAT
Timer Status
0 = Reset
1 = Run
2 = Hold
3 = End
23
SP1
Setpoint 1
NB – do not write continuously changing values to this variable. The memory technology used in this product has a
limited (100,000) number of write cycles. If ramped setpoints are required, consider using the internal ramp rate function
or the remote comms setpoint (Modbus address 26 )in preference.
24
SP2
Setpoint 2
NB – do not write continuously changing values to this variable. The memory technology used in this product has a
limited (100,000) number of write cycles. If ramped setpoints are required, consider using the internal ramp rate function
or the remote comms setpoint (Modbus address 26 )in preference.
25
OP.HI
Output High Limit
30
OP.LO
Output Low Limit
31
SP.RAT
Setpoint Rate Limit Value (0 = no rate limit)
35
StAt
Instrument Status. This is a bitmap:
B0 – Alarm 1 Status
B1 – Alarm 2 Status
B2 – Alarm 3 Status
B3 – Alarm 4 Status
B4 – Auto/Manual Status
B5 – Sensor Break Status
B6 – Loop Break Status
B7 – CT Low load current alarm status
B8 – CT High leakage current alarm status
B9 – Program End
B10 – PV Overrange (by > 5% of span)
B11 – CT Overcurrent alarm status
B12 – New Alarm Status
B13 – Timer/Ramp Running
B14 – Remote (comms) SP Fail
B15 – Autotune Status
In each case, a setting of 1 signifies ‘Active’, 0 signifies ‘Inactive’.
75
A3.---
Alarm 3 Threshold
81
A4.---
Alarm 4 Threshold
82
Home
Home Display.
0 – Standard PV and SP display
1 – PV and Output Power display
2 – PV and Time remaining display
3 – PV and Timer elapsed time display
4 – PV and Alarm 1 setpoint
5 – PV and Load Current
6 – PV only
7 – PV and Composite SP/Time remaining
106