Default output range, Formulas for calculation of output values, Output configurations – ROTRONIC CF8-W-Disp-GH User Manual
Page 3

Dokument
UMA 146
Rev
1
Page
3 (7)
Terminal
Default
Output
Default Output
Range
Outputs of this
sensor
Output Range of
this sensor
Out(1)
0-10VDC
0-2000 ppm CO
2
0-10VDC
0-4 % CO
2
Out(2)
0-10VDC
0-50
o
C
Relay
Closed
Open
> 1000 ppm CO
2
< 900 ppm CO
2
> 2,0 % CO
2
< 1,9 % CO
2
Table I. Default output configurations for
CF8-W-Disp-GH
Formulas for calculation of output values
Configuration
Output Range
Formula for calculation
0-10 VDC
0-2000 ppm CO
2
0-50
o
C
CO
2
value = Volt/10*2000
Temperature value in
o
C = Volt/10*50
2-10 VDC
0-2000 ppm CO
2
0-50
o
C
CO
2
value = (Volt –2)/8*2000
Temperature value in
o
C = (Volt –2)/8*50
4-20 mA
0-2000 ppm CO
2
0-50
o
C
CO
2
value = (mA-4)*2000/16
Temperature value in
o
C = (mA-4)*50/16
a-b
c–d
Value = (reading-a)/(b-a)*(d-c)+c
a = lowest value of the configuration
b = highest value of the configuration
c = lowest value of the range
d = highest value of the range
Table II. Calculation of CO
2
value and temperature value for
CF8-W-Disp-GH
The red LED is lit when the relay output is closed.
Output Configurations
The sensors/controllers are supplied from the factory (unless otherwise ordered) with
0...10VDC linear outputs for Out(1) and Out(2) (see Table I). If other options are
needed for the application, the output jumpers have to be configured before the unit
is powered up. Each jumper selection is independent from the others, except for the
“Start point selection” jumper, which affects both, Out(1) and Out(2), linear outputs.