Electrical connections

The power supply has to be connected to

and

.

is considered as

system ground. If the analogue output is connected to a controller the same ground
reference has to be used for
the CF5-W unit and for the control system! Unless
different transformers are used, special precautions need to be taken.


PLEASE NOTE! The CF5-W signal and power supply
grounds are common

PLEASE NOTE!
The same ground reference has to be used for
the
CF5-W

unit and for the control system!

If possible keep the sensor powered up after mounting. Connect the analogue output
before measuring.

Connection

Terminal

Function

Electrical Data

Remarks

Power (+)


Power ground (-)

24 VAC/DC+ (+-

20%), 3W

24 VAC/DC-

2W without output load
See note 1!

Out(1)



Out(2)

Analogue Output 1 (+)



Analogue Output 2 (+)

0-10 VDC or 0-20

mA,

2-10 VDC or 4-20

mA,

Same as Output 1


According to positions of
Out(1) and start point
jumpers. See note 2!


According to positions of
Out(2) and start point
jumpers. See note 2 and
3!


Note 1: The ground terminal is used as negative power supply DC input or AC phase
ground

(half wave rectifier).


Note 2: CF5-W can deliver a voltage or a current loop for Out(1) / Out(2). To change
between voltage and current output mode the hardware jumpers are used. There is one
jumper for Out(1) and one for Out(2), so that one output can be a voltage output and the
other a current output. Both, voltage output and current output can have start points 0 % (0-
10 VDC or 0-20mA) or 20% (2-10 VDC or 4-20mA). The same start point is used for both
outputs. See the function manual.


Note 3: Please use voltage outputs for temperature measurements. The accuracy of temperature
measurements is valid only for units configured in voltage outputs mode.

~

+

~

+