4

INS

TRUC

TION

Type ETO2

Supply voltage to actuator

(mixing valve) .................................max. 48 V AC/DC / max. 2 A

On/off differential ........................................................1.8°F / 1°C

Temperature range .................................... -4/+50°F / -20/+10°C

Ambient temperature .................................... 32/122°F / 0/+50°C

Ambient air humidity .......................................................10-95%

Enclosure rating .....................................................

Nema 1- IP 20

Weight .............................................................

17.46 oz - 600 g

Dimensions H/W/D ...........

3.54/6.14/1.77 Inches - 90/156/45 mm

Type

................................................................................. 1B

Control pollution degree ............................................................2

Rated impulse voltage .......................................................... 4 kV

Ground sensor - type ETOG-55:

Designed to be embedded in outdoor surfaces.

Detection ............................................ Moisture and temperature

Mounting ..........................................................Outdoor surfaces

Enclosure rating .................................................

NEMA 6P - IP 68

Ambient temperature ............................. -57/+158°F / -50/+70°C

Dimensions

H/Ø................................1.26/2.36 Inches - 32/60 mm

Ground sensor - ETOG-56/ETOk-1:

Designed to be embedded in outdoor surfaces.

Detection ........................................... Moisture and temperature

Mounting .........................................................Outdoor surfaces

Enclosure rating .................................................

NEMA 6P - IP 68

Ambient temperature ............................. -57/+158°F /-50/+70°C

Dimensions, sensor H/Ø .................

1.26/2.36 Inches - 32/60 mm

Dimensions, tube

H/Ø ...................3.07/2.50 Inches - 78/63,5 mm

Gutter sensor - type ETOr-55:

Designed to be mounted in gutter or downpipe. Is used together

with outdoor sensor type ETF-744/99.

Detection ........................................................................Moisture

Mounting ...................................................... Gutter or downpipe

Enclosure rating .................................................

NEMA 6P - IP 68

Ambient temperature ............................. -57/+158°F / -50/+70°C

Dimensions H/W/D ...........

4.13/1.18/0.51 Inches - 105/30/13 mm

Outdoor sensor - ETf-744/99:

Detection ................................................................. Temperature

Mounting ...............................................................................Wall

Enclosure rating ...................................................

NEMA 3 - IP 54

Ambient temperature ............................. -57/+158°F / -50/+70°C

Dimensions H/W/D .............

3.39/1.77/1.38 Inches - 86/45/35 mm

water pipe sensor - ETf-522:

Detection ................................................................. Temperature

Mounting ...........................................................Strapped to pipe

Enclosure rating ...................................................

NEMA 3 - IP 54

Ambient temperature ........................... -40/+248°F / -40/+120°C

Dimensions

Ø/L ...............................0,26/1.97 Inches - 6,5/50 mm

NOTE: The snow and ice melting system is deactivated

in the event of sensor failure - regardless of sensor type.

sEnsOr InsTallaTIOn

Ground sensor - ETOG, figs 1+3:

For installation in outdoor surfaces where ice and snow are a

regular problem. The sensor must be embedded horizontally

with its top flush with the surrounding surface.

The sensor cable must be installed in accordance with current

regulations.

NOTE: We strongly recommend the use of cable pipes in order

to protect the sensor cable. Detailed installation instructions are

supplied with the sensor.

With ETOG-55, use the accompanying installation plate.
With ETOG-56, use the ETOK-1 mounting kit.

NOTE: Remove the installation plate from ETOG-55

before initial start-up.

Gutter sensor - ETOr, figs 2+4:

For installation in a gutter or downpipe on the sunny side of

the building. It is important to ensure that the sensor contact

elements face against the flow of melt water. If necessary,

two sensors can be installed in parallel. Detailed installation

instructions are supplied with the sensor.

Note that the pink and grey wires are not used.

Outdoor sensor - ETf-744/99, figs 2+4:

Although ETF is designed for use with gutter sensor ETOR, it

can also be used separately for the detection of temperature

alone. The sensor should be mounted on the wall beneath the

eaves on the north side of the building.

water pipe sensor - ETf-522:

Is only used with hydronic heating systems to detect the

temperature of the supply and return water. Must be fastened to

the pipe directly with strips.

sensor cables:

With the exception of ETOG-56, which has a

32.8 ft

(10 m)

cable, ETOG and ETOR sensors are supplied with a

82.02 ft

English / Instruction