ADJUSTMENT PROCEDURE
1. using wrench or power, rotate the actuator shaft to extreme clockwise position
for direct drive applications. For linear applications, operate actuator to full closed
position. All switches should change to their appropriate functions.
2. The cam can be relocated and repositioned by loosening the set screw. To adjust
manual cams grasp cam on knurled segment of cam surface. rotate cam clock-
wise or counterclockwise to obtain correct actuation point. Feeling or sound of
clicks indicates incremental adjustments. Applying pressure on cam in direction of
actuation segment of cam surface, and rotating, eliminates incremental adjust-
ments. Stop rotating and release pressure on the cam when it is at proper actua-
tion point; this allows engagement of cam to spline. Check circuit to verify contact
at proper point. rotate the shaft counterclockwise. repeat all steps above as nec-
essary. Lock cam on spine with set screw provided for additional security.
3. Operate actuator to extreme opposite position to verify correct operation of
switch(es). readjust as required.
4. replace OPen/CLOSeD indicator drum making sure incoming wires are tucked
in so as not to rub against the drum. replace cover window making sure it lines up
correctly with indicator to display the proper indication of valve position. replace
snap-on cover.
WIRING
Complete all electrical wiring in accordance with Local and national Codes. Tighten
all screws. (Sealed leads are provided from the factory on request).
MAINTENANCE
The Series QV rotary Position indicator/Switch is not field serviceable and should
be returned if repair is needed (field repair should not be attempted and may void
warranty). Be sure to include a brief description of the problem plus any relevant
application notes. Contact customer service to receive a return goods authorization
number before shipping.
PROXIMITY CONTROLS
Phone: 219/879-8000
www.dwyer-inst.com
A DIVISION OF DWYER INSTRUMENTS, INC.
Fax: 219/872-9057
e-mail: [email protected]
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Disconnect supply circuit before opening. Keep unit tightly
closed while circuits are alive.
CAUTION