Amerex 14795 User Manual
Page 8

8
NOTE: In the Recovery/Recharge procedure, it will be
impossible to completely empty the recovery
cylinder contents. A heal in the recovery
cylinder of up to 1 pound is normal and should
be expected. If recovering a full extinguisher
(leaker), the need for an additional supply of
Halotron I agent should be anticipated so that
the extinguisher may be brought back to its full
charged weight. If the Halotron I in the
Recovery Cylinder will not be used immediately,
the cylinder should be stored with 95
– 100 psig
argon pressure maintained to keep the Halotron
I/argon mix in solution. The pressure should be
checked once a week or more frequently.