SHUT DOWN INSTRUCTIONS
After following the above procedure, there may be a small amount of Halotron I left in the
charging hose. If it will be more than 8 hours before another extinguisher will be filled,
Amerex recommends bleeding this Halotron I off into the atmosphere. The bleed off
process will prolong the life of your recharge equipment.
Follow this procedure to remove Halotron I captured in the charging hose:
1. Make sure that the Halotron I recharge cylinder is CLOSED.
2. Point the male quick connect plug for the argon supply away from yourself and
others and open the toggle valve. A small amount of Halotron I and argon may be
discharged. Close the toggle valve. The charging hose is now empty of Halotron I
and argon pressure.